| Date |
Text |
| 2010-12-22 09:09:57 | 2223 PALM BEACH LAKES BOULEVARD, SUITE #102 | | | PERMIT #10120311 | | | MASTER #08010251 | | | REVIEW COMMENTS - FIRE | | | | | | | | | THE SUITE NUMBER ON THE PERMIT APPLICATION AND THE | | | SUITE NUMBER ON THE PLANS ARE CONFLICTING (SUITE | | | 101/102). | | | | | | INSUFFICIENT NUMBER OF NOTIFICATION APPLIANCES SHOWN IN | | | CORRIDORS. | | | | | | NOTIFICATION APPLIANCES NOT PROVIDED IN KITCHENETTE OR | | | PREP ROOM. | | | | | | THE STROBE DEVICE CANNOT BE SEEN FROM THE | | | ADA-ACCESSIBLE TOILET AREA IN THE WOMEN'S BATHROOM. | | | | | | DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM CONDITION. | | | | | | INDICATE THE CLASS AND STYLE OF WIRING. | | | | | | INDICATE THE SIZE OF THE BATTERY TO BE INSTALLED. | | | | | | VOICE EVACUATION MESSAGE TO ANNOUNCE AN EMERGENCY HAS | | | BEEN REPORTED IN THE BUILDING, PERSONS ARE TO LOCATE | | | THE NEAREST EXIT AND EXIT THE BUILDING IMMEDIATELY. | | | | | | DEVICES LABELED AS AAL DO NOT INDICATE THE NOTIFICATION | | | APPLIANCES ARE SPEAKER/STROBES. | | | | | | INDICATE IF ANY TAMPER SWITCHES OR FLOW SWITCHES FROM | | | THE FIRE SPRINKLER SYSTEM WILL BE MONITORED BY THE FIRE | | | ALARM SYSTEM. | | | | | | FIRE ALARM SYSTEM TO BE MONITORED BY UL LISTED CENTRAL | | | STATION MONITORING COMPANY. | | | | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|