2010-12-22 09:09:572223 PALM BEACH LAKES BOULEVARD, SUITE #102
 PERMIT #10120311
 MASTER #08010251
 REVIEW COMMENTS - FIRE
  
  
 THE SUITE NUMBER ON THE PERMIT APPLICATION AND THE
 SUITE NUMBER ON THE PLANS ARE CONFLICTING (SUITE
 101/102).
  
 INSUFFICIENT NUMBER OF NOTIFICATION APPLIANCES SHOWN IN
 CORRIDORS.
  
 NOTIFICATION APPLIANCES NOT PROVIDED IN KITCHENETTE OR
 PREP ROOM.
  
 THE STROBE DEVICE CANNOT BE SEEN FROM THE
 ADA-ACCESSIBLE TOILET AREA IN THE WOMEN'S BATHROOM.
  
 DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 INDICATE THE CLASS AND STYLE OF WIRING.
  
 INDICATE THE SIZE OF THE BATTERY TO BE INSTALLED.
  
 VOICE EVACUATION MESSAGE TO ANNOUNCE AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, PERSONS ARE TO LOCATE
 THE NEAREST EXIT AND EXIT THE BUILDING IMMEDIATELY.
  
 DEVICES LABELED AS AAL DO NOT INDICATE THE NOTIFICATION
 APPLIANCES ARE SPEAKER/STROBES.
  
 INDICATE IF ANY TAMPER SWITCHES OR FLOW SWITCHES FROM
 THE FIRE SPRINKLER SYSTEM WILL BE MONITORED BY THE FIRE
 ALARM SYSTEM.
  
 FIRE ALARM SYSTEM TO BE MONITORED BY UL LISTED CENTRAL
 STATION MONITORING COMPANY.
  
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW