| Plan Review Notes For Permit 10120293 |
| Permit Number |
10120293 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-13 09:23:03 | PROVISO: | | | ELECTRIC SUB PERMIT REQUIRED FOR THE NEW ELECTRIC WORK. | | | ELECTRICAL BOXES INSTALLED WITHIN FIRE RATED WALLS MUST | | | BE FIRE STOPPED, PROTECTED, LISTED, OR INSTALLED TO | | | MAINTAIN THE FIRE RESISTANCE RATING. PROVIDE A DETAIL | | | OR SPECIFICATION FOR THE INSTALLATION. NEC 300.21 | | | ROBERT LECKY, ELECTRICAL PLANS EXAMINER, 561-805-6718 |
|