| Plan Review Notes For Permit 10120284 |
| Permit Number |
10120284 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-15 16:20:26 | 505 SOUTH FLAGLER DRIVE, SUITE #700 | | | PERMIT #10120284 | | | REVIEW COMMENTS - FIRE | | | | | | | | | FIRE ALARM NOTIFICATION APPLIANCES WILL BE ADDED TO THE | | | RESTROOMS AS PART OF THE BASE-BUILDING FIRE ALARM | | | UPGRADE (UNDER A SEPARATE DRAWING AND PERMIT). | | | | | | PLANS SHOW FIRE ALARM SPEAKER/STROBE DEVICES. SUBMITTED | | | PRODUCT DATA SHOWS FIRE ALARM HORN/STROBE DEVICES. FIRE | | | ALARM SYSTEM HAS VOICE EVACUATION CAPABILITIES | | | REQUIRING SPEAKER/STROBE NOTIFICATION APPLIANCES. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|