Plan Review Notes
Plan Review Notes For Permit 10120203
Permit Number 10120203
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-14 11:08:27901--45TH STREET (CATH LAB)
 PERMIT #10120203
 REVIEW COMMENTS - FIRE
  
 PROVIDE TEMPORARY SPRINKLER COVERAGE FOR SMALL
 TEMPORARY VESTIBULE CREATED WEST OF THE PROCEDURE ROOM.
  
 SYSTEM PRESSURES EXCEED 100 PSI. PROVIDE APPROPRIATE
 HANGER RESTRICTIONS AND SPACING PER NFPA 13.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730