| 2010-12-14 11:08:27 | 901--45TH STREET (CATH LAB) | | | PERMIT #10120203 | | | REVIEW COMMENTS - FIRE | | | | | | PROVIDE TEMPORARY SPRINKLER COVERAGE FOR SMALL | | | TEMPORARY VESTIBULE CREATED WEST OF THE PROCEDURE ROOM. | | | | | | SYSTEM PRESSURES EXCEED 100 PSI. PROVIDE APPROPRIATE | | | HANGER RESTRICTIONS AND SPACING PER NFPA 13. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|