| Plan Review Notes For Permit 10120201 |
| Permit Number |
10120201 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-16 13:48:13 | DENIED BY PLUMBING | | | | | | 2004 FBC W/2009 REVISIONS | | | RESIDENTIAL POOL | | | | | | DENIED BY PLUMBING | | | | | | 1) THE SIMPLIFIED TDH CALCULATIONS SPECIFY A 3/4 HP | | | PENTAIR POOL PUMP AND THE LANDSCAPE AND POOL PLAN | | | SPECIFIES A 1 HP PENTAIR PUMP. SUBMIT 2 COPIES OF THE | | | SPECIFICATIONS FOR THE POOL PUMP INCLUDING THE PUMP | | | CURVE FOR THE PUMP THAT WILL BE INSTALLED. IF A | | | VARIABLE SPEED OR TWO SPEED PUMP IS USED USE THE MAX. | | | PUMP FLOW IN CALCULATIONS. | | | | | | 2) THE PENTAIR SUPERFLO SERIES 3/4 HP PUMP AT HIGH | | | SPEED HAS A FLOW RATE OF ABOUT 65 GPM WITH A TDH OF | | | 21.3. AT 65 GPM IN 1-1/2" PIPE THE WATER VELOCITY IS | | | 10.23 FPS. WHICH EXCEEDS THE 6 FPS ALLOWED IN MAIN | | | DRAIN BRANCH PIPING. EVEN AT THE 33 GPM SPECIFIED ON | | | THE PLANS THE VELOCITY IS 13 GPM IN 1" PIPE, WHICH | | | EXCEEDS THE 8 FPS ALLOWED IN THE SUCTION LINE AND THE | | | 10 FPS ALLOWED IN THE RETURN LINES. PLEASE CORRECT. | | | | | | 3) PROVIDE TWO SETS OF A POOL PLAN THAT INDICATES THE | | | LOCATIONS OF THE MAIN DRAINS, THE RETURNS, SKIMMER, | | | POOL LIGHT, ETC. | | | | | | 4) IF A POOL HEATER WILL BE INSTALLED, SUBMIT TWO SETS | | | OF MANUFACTURER'S SPECIFICATIONS FOR THE HEATER | | | INDICATING THE ELECTRICAL OR GAS REQUIREMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | |
|