Plan Review Notes
Plan Review Notes For Permit 10120201
Permit Number 10120201
Review Stop P
Sequence Number 1
Notes
Date Text
2010-12-16 13:48:13DENIED BY PLUMBING
  
 2004 FBC W/2009 REVISIONS
 RESIDENTIAL POOL
  
 DENIED BY PLUMBING
  
 1) THE SIMPLIFIED TDH CALCULATIONS SPECIFY A 3/4 HP
 PENTAIR POOL PUMP AND THE LANDSCAPE AND POOL PLAN
 SPECIFIES A 1 HP PENTAIR PUMP. SUBMIT 2 COPIES OF THE
 SPECIFICATIONS FOR THE POOL PUMP INCLUDING THE PUMP
 CURVE FOR THE PUMP THAT WILL BE INSTALLED. IF A
 VARIABLE SPEED OR TWO SPEED PUMP IS USED USE THE MAX.
 PUMP FLOW IN CALCULATIONS.
  
 2) THE PENTAIR SUPERFLO SERIES 3/4 HP PUMP AT HIGH
 SPEED HAS A FLOW RATE OF ABOUT 65 GPM WITH A TDH OF
 21.3. AT 65 GPM IN 1-1/2" PIPE THE WATER VELOCITY IS
 10.23 FPS. WHICH EXCEEDS THE 6 FPS ALLOWED IN MAIN
 DRAIN BRANCH PIPING. EVEN AT THE 33 GPM SPECIFIED ON
 THE PLANS THE VELOCITY IS 13 GPM IN 1" PIPE, WHICH
 EXCEEDS THE 8 FPS ALLOWED IN THE SUCTION LINE AND THE
 10 FPS ALLOWED IN THE RETURN LINES. PLEASE CORRECT.
  
 3) PROVIDE TWO SETS OF A POOL PLAN THAT INDICATES THE
 LOCATIONS OF THE MAIN DRAINS, THE RETURNS, SKIMMER,
 POOL LIGHT, ETC.
  
 4) IF A POOL HEATER WILL BE INSTALLED, SUBMIT TWO SETS
 OF MANUFACTURER'S SPECIFICATIONS FOR THE HEATER
 INDICATING THE ELECTRICAL OR GAS REQUIREMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  