| 2010-12-20 18:55:35 | ****PROVISOS OUTSTANDING**** |
| | ****REVISION REQUIRED**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. ADDRESSED |
| | |
| | 2. FAC9B72, PRODUCT APPROVALS REVIEWED BY DESIGNER OF |
| | RECORD REQUIRED FOR ALL COMPONENTS AND CLADDING AND |
| | STRUCTURAL COMPONENTS SUCH AS: |
| | |
| | SIDING, FRONT DOOR, GARAGE DOOR, HELICAL PIERS |
| | |
| | ANY OTHER PRODUCT APPROVALS NOT YET REVIEWED ARE TO BE |
| | SUBMITTED AS A REVISION PRIOR TO INSTALLATION. |
| | |
| | 3. ADDRESSED. |
| | |
| | 4. SHEET A8, STUCCO TO BE < 5/8" OR ALLOW 6" FOR |
| | INSPECTION FOR TERMITES, FBC R704.1. |
| | |
| | 5. ADDRESSED. |
| | |
| | 6. ENGINEER TO PROVIDE A LETTER OR REVISE THE PLAN TO |
| | CONFIRM THAT THE DESIGN CONFORMS TO THE REQUIREMENT OF |
| | FBC R301.2.1.4.3(2), "ROOF SHEATHING UPLIFT AND |
| | ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED BY 20 |
| | PERCENT." |
| | |
| | 7. SUBMIT A REVISED, CORRECTED ELEVATION CERTIFICATE |
| | (DISCUSSED WITH CHRIS, COMPASS SURVEYING). THE REVISED |
| | "CONSTRUCTION DRAWINGS" ELEVATION CERTIFICATE IS TO BE |
| | SUBMITTED WITH THE REVISION PRIOR TO CONCRETE POUR. |
| | |
| | 8. MECHANICAL PLANS REQUIRED WITH SUBMISSION OF |
| | MECHANICAL PERMIT. MECHANICAL PLANS TO INCLUDE PROPOSED |
| | ELEVATION OF NEW AND EXISTING EQUIPMENT. |
| | |
| | NEW PROVISO ITEM: |
| | |
| | 9. PLUMBING CHANGES TO BE SUBMITTED ON "P" SHEETS IF |
| | REQUIRED |
| | |