2010-12-20 18:55:35****PROVISOS OUTSTANDING****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. ADDRESSED
  
 2. FAC9B72, PRODUCT APPROVALS REVIEWED BY DESIGNER OF
 RECORD REQUIRED FOR ALL COMPONENTS AND CLADDING AND
 STRUCTURAL COMPONENTS SUCH AS:
  
 SIDING, FRONT DOOR, GARAGE DOOR, HELICAL PIERS
  
 ANY OTHER PRODUCT APPROVALS NOT YET REVIEWED ARE TO BE
 SUBMITTED AS A REVISION PRIOR TO INSTALLATION.
  
 3. ADDRESSED.
  
 4. SHEET A8, STUCCO TO BE < 5/8" OR ALLOW 6" FOR
 INSPECTION FOR TERMITES, FBC R704.1.
  
 5. ADDRESSED.
  
 6. ENGINEER TO PROVIDE A LETTER OR REVISE THE PLAN TO
 CONFIRM THAT THE DESIGN CONFORMS TO THE REQUIREMENT OF
 FBC R301.2.1.4.3(2), "ROOF SHEATHING UPLIFT AND
 ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED BY 20
 PERCENT."
  
 7. SUBMIT A REVISED, CORRECTED ELEVATION CERTIFICATE
 (DISCUSSED WITH CHRIS, COMPASS SURVEYING). THE REVISED
 "CONSTRUCTION DRAWINGS" ELEVATION CERTIFICATE IS TO BE
 SUBMITTED WITH THE REVISION PRIOR TO CONCRETE POUR.
  
 8. MECHANICAL PLANS REQUIRED WITH SUBMISSION OF
 MECHANICAL PERMIT. MECHANICAL PLANS TO INCLUDE PROPOSED
 ELEVATION OF NEW AND EXISTING EQUIPMENT.
  
 NEW PROVISO ITEM:
  
 9. PLUMBING CHANGES TO BE SUBMITTED ON "P" SHEETS IF
 REQUIRED
  