| 2010-12-15 14:06:19 | VERIFY IN WRITING THAT THE MAIN ELECTRICAL SERVICE WILL | | | CARRY THE ADDITIONAL ELECTRICAL LOAD CREATED BY ADDING | | | TANKLESS WATER HEATER IN UNIT 2502. THE MAIN ELECTRIC | | | SERVICE DEMAND MUST BE SIZED FOR THE INCREASED LOAD. | | | THE ELECTRIC UTILITY NEEDS TO VERIFY THE INCOMING | | | SERVICE AND TRANSFORMER HAVE THE CAPACITY TO HANDLE | | | TANKLESS WATER HEATING AS A STANDARD RETO FIT FOR THIS | | | BUILDING. | | | | | | ROBERT LECKY, PLANS EXAMINER 561 805-6718 |
|