| 2010-12-14 08:57:19 | BUILDING PLAN REVIEW |
| | PERMIT: 10120173 |
| | ADD: 5200 N FLAGLER #2502& 2503 |
| | CONT: A&A DEVELOPMENT GROUP LLC |
| | TEL: (561)719-0895 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | (CONDOMINIUM SUITES) WHICH COMBINE TO FORM 'THE SITE'. |
| | A 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY |
| | COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF OF |
| | TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE |
| | REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. |
| | |
| | 2) MASTER BATH SHOWER TENANT SEPERATION WALLS. FBC-B |
| | 1207.2 AIR BORNE SOUND REQUIREMENTS. |
| | |
| | 3) THIS IS ONLY IF ADDITIONAL FLOORING IS TO BE |
| | APPLIED. FBC-B 1207.3 STRUCTURE BORNE SOUND |
| | REQUIREMENTS, MUST MEET THE SOUND INSULATION OF 50 STC. |
| | |
| | 4) MASTER BATH SHOWER TO MEET THE REQUIREMENTS OF FBC-B |
| | 2509.2 BASE FOR TILE: SHOWER, EITHER CEMENT, |
| | FIBER-CEMENT, OR GLASS MAT GYPSUM AS A BACKING BOARD. |
| | |
| | JIM WITMER C. B. O. |