2010-12-09 10:00:57222 LAKEVIEW AVENUE - 14TH FLOOR COMMON AREA
 TRACKING #10120067
 PERMIT #10100194
 REVIEW COMMENTS - FIRE
  
 HANGERS ARE REQUIRED FOR ARMOVERS EXCEEDING 12-INCHES
 WHEN SYSTEM PRESSURES EXCEED 100 PSI.
  
 RESTROOM SPRINKLERS LOCATED CLOSER THAN SIX FEET APART.
 SPRINKLER LOCATIONS MAY NEED TO BE STAGGERED TO PREVENT
 COLD SOLDERING.
  
 ELEVATOR LOBBY SPRINKLERS TO COMPLY WITH THE
 OBSTRUCTION RULES OF NFPA 13 CONCERNING THE ELEVATOR
 LOBBY SOFFITS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW