| 2010-12-29 15:33:38 | SANITATION: |
| | |
| | 1. PLEASE INCLUDE IN YOUR PLAN A COPY OF CITY STANDARD |
| | DUMPSTER DETAIL. ONE CAN BE OBTAINED FROM: |
| | HTTP://WWW.CITYOFWPB.COM/ENGINEERING/PDF/STANDARDS/GC-8 |
| | .PDF |
| | THIS WILL HELP YOU WITH CONSTRUCTING TO MINIMUM |
| | DIMENSIONS OUR CITY VEHICLES NEED TO OPERATE. |
| | 2. INTERIOR DIMENSIONS OF THE ENCLOSURE MUST BE A |
| | MINIMUM OF 12'-6" WIDE AND 12' DEEP. A CONCRETE PARKING |
| | STOP BAR 10' LONG MUST BE CENTERED (FROM GATES) AND |
| | INSTALLED 18" FROM THE BACK WALL. STEEL BARS WILL NEED |
| | TO BE DRILLED THRU THE STOP BAR AND INTO THE INTERIOR |
| | FLOOR OF THE ENCLOSURE TO STOP THE STOP BAR FROM MOVING |
| | WHEN THE DUMPSTER IS SET INSIDE. |
| | 3. DUMPSTER ENCLOSURE MUST HAVE A MINIMUM OF 12'-6" |
| | OPENING BETWEEN THE GATE POSTS. |
| | 4. IT IS STRONGLY SUGGESTED THAT YOU ADD A RECYCLING |
| | CENTER TO YOUR DUMPSTER ENCLOSURE, ESPECIALLY SINCE YOU |
| | WILL BE CHARGED FOR RECYCLING, WHETHER YOU USE IT OR |
| | NOT. A RECYCLING CENTER WILL CALL FOR A LARGER |
| | ENCLOSURE. |
| | 5. THE OPENING OF THE DUMPSTER ENCLOSURE MUST BE ANGLED |
| | SO THAT A 40' LONG TRUCK WITH THE FORKS EXTENDED CAN |
| | APPROACH THE OPENING AND PICK UP THE DUMPSTER WITHOUT |
| | MAKING A SHARP TURN OR A THREE POINT TURN. |
| | 6. THE TRUCK NEEDS TO HAVE NO LESS THAN A 26' HIGH |
| | VERTICAL CLEARANCE AREA FOR THE TRUCK TO PICK UP THE |
| | DUMPSTER. THIS IS THE CLEAR AREA OVER THE DUMPSTER AND |
| | WHERE THE TRUCK WILL BE STOPPED TO UNLOAD THE DUMPSTER. |
| | 7. THE TRUCK NEEDS TO HAVE NO LESS THAN 14' HIGH |
| | VERTICAL CLEARANCE AND 12' HORIZONTAL CLEARANCES FOR |
| | THE TRUCK TO DRIVE THROUGH. |
| | 8. NO FLOOR DRAIN TO THE SANITARY SEWER CAN BE |
| | INSTALLED IN THE DUMPSTER ENCLOSURE. |
| | 9. THE DUMPSTER ENCLOSURE MUST BE LOCATED TO ALLOW THE |
| | DUMP TRUCK TO BACK UP NO MORE THAN 50' STRAIGHT BACK |
| | AFTER RESETTING THE DUMPSTER IN THE ENCLOSURE. |
| | 10. PREVIOUS DUMSPTER AREA WILL REMAIN? REMOVE? PLEASE |
| | INCLUDE A SUMMARY EXPLAINING THIS. IT MAY CHANGE YOUR |
| | PERVIOUS TO IMPERVIOUS CALCULATIONS WHICH WILL CHANGE |
| | YOUR STORMWATER ACCOUNT. |
| | |
| | |
| | MANUEL JULIAN GONZALEZ |
| | CSD ENGINEERING REVIEW |
| | 401 CLEMATIS STREET, 1ST FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | |
| | |