| 2010-12-03 16:57:17 | 801 SOUTH OLIVE AVENUE, UNIT #706 | | | PERMIT #10120033 | | | MASTER #10080601 | | | REVIEW COMMENTS - FIRE | | | | | | A HIGH-RISE APARTMENT BUILDING EXISTS AT THIS ADDRESS; | | | THEREFORE, THE SYSTEM MUST BE DESIGNED ACCORDING TO | | | NFPA 13. SEVERAL GENERAL NOTES MAKE REFERENCE TO NFPA | | | 13R WHICH IS APPLICABLE ONLY TO RESIDENTIAL OCCUPANCIES | | | UP TO (AND INCLUDING) FOUR STORIES IN HEIGHT. | | | | | | SPRINKLER PROTECTION IS REQUIRED IN CLOSESTS AND | | | PANTRIES PER NFPA 13 SECTION 8.14.8.2 (2002 EDITION). | | | SPRINKLERS ARE NOT REQUIRED IN THESE SPACES IF THE | | | DWELLING UNIT IS LOCATED WITHIN A HOTEL OR MOTEL. | | | | | | PROVIDE HYDRAULIC CALCULATIONS FOR THE FOUR MOST | | | DEMANDING SPRINKLERS PER NFPA 13 SECTION 11.2.3.5. | | | | | | THE THREE NEW RESIDENTIAL SIDEWALL SPRINKLERS SUPPLIED | | | BY THE BRANCH LINE DO NOT APPEAR TO BE CONNECTED TO THE | | | REST OF THE SYSTEM. | | | | | | SPRINKLER PROTECTION IS REQUIRED BELOW SOFFITS GREATER | | | THAN 8-INCHES IN WIDTH WHEN SIDEWALL SPRINKLERS ARE | | | LOCATED IN THAT SOFFIT PER NFPA 13 SECTION 8.7.4.1.3.2. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|