| 2010-12-02 13:13:40 | BUILDING PLAN REVIEW |
| | PERMIT: 10110699 |
| | ADD: 1300 ALLENDALE RD |
| | CONT: INSULPRO, INC. |
| | TEL: (813)486-8164 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE INFORMATION AS TO IF THE BUILDING IS |
| | FULLY SPRINKLERED? IT WILL DETERMINE WHICH OF THE CODE |
| | SECTIONS WHICH THIS PROJECT WOULD BE REVIEWED. FOR THIS |
| | REVIEW IT WILL BE CONSIDERED FIRE SPRINKLERED. |
| | |
| | 2) THE FOLLOWING INFORMATION WILL REQUIRED TO COMPLETE |
| | THE REVIEW FOR THE CONSTRUCTION OF A WALK IN FREEZER |
| | AND COMPLIANCE WITH SECTION 2007 W/2009 SUPPLEMENTS |
| | FBC-B2603.4.1.2.: |
| | 2603.4.1.2 COOLER AND FREEZER WALLS. FOAM PLASTIC |
| | INSTALLED IN A MAXIMUM THICKNESS OF 10 INCHES (254 MM) |
| | IN COOLER AND FREEZER WALLS SHALL: |
| | |
| | 2.1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE |
| | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. |
| | |
| | 2.2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES |
| | OF NOT LESS THAN 600??F AND 800??F (316??C AND 427??C), |
| | RESPECTIVELY. |
| | |
| | 2.3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 |
| | MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT |
| | ANY POINT. ARE THE PANELS TO BE CONSTRUCTED FROM STEEL |
| | OR ALUMINUM? PLEASE MARK THE PLANS AS SUCH. |
| | |
| | 2.4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. |
| | WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH |
| | THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN |
| | WHICH IT IS LOCATED SHALL BE SPRINKLERED. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |