| Plan Review Notes For Permit 10110685 |
| Permit Number |
10110685 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2011-03-14 10:19:27 | REVISION REQUIRED | | | | | | 1. THIS AREA OF PLUMBING HAS A MIXTURE OF WASTE STACK | | | VENTING AND SOVENT PIPING. | | | SOVENT IS AN ENGINEERED SYSTEM. CONNECTIONS DOWNSTREAM | | | OF THE DEAERATOR VENT MAY BE MADE WITHOUT | | | RE-ENGINEERING THE SYSTEM. CONNECTING INTO THE BUILDING | | | DRAIN OR BUILDING DRAIN BRANCHES WOULD ALSO BE | | | PERMISSIBLE. | | | | | | 2. IF STUDOR VENTS ARE USED, THEN A RELIEF VENT WILL BE | | | REQUIRED. | | | 917.3.2 | | 2011-03-14 10:18:26 | REVISION REQUIRED | | | | | | |
|