| Plan Review Notes For Permit 10110665 |
| Permit Number |
10110665 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-07 08:59:38 | PLAN DENIED | | | EXHAUST DUCT NOTE # 2 AND THE PLANS DO NOT MATCH ,REFER | | | TO SECTION 506.3.1.1 GREASE DUCT MATERIALS. 2007 FBC | | | (M). | | | SHALL HAVE MIN. 10 FT. DISTANCE FROM THE BOTTOM OF THE | | | EXHAUST DUCT TO THE GRADE . REFER TO SECTION 506.3.12.3 | | | 2007 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732. |
|