| Plan Review Notes For Permit 10110644 |
| Permit Number |
10110644 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2011-02-11 14:52:10 | ****PROVISOS**** | | | ****REVISION REQUIRED**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | | | | 1. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS | | | DOOR, EXTERIOR DOORS, FAC9N-3. SUBMIT PRODUCT APPROVALS | | | AS A REVISION PRIOR TO INSTALLATION. | | | | | | 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP | | | DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN | | | /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH NFIP | | | REQUIREMENTS IS REQUIRED. PRIOR TO FINAL INSPECTION, | | | PROVIDE A "FINISHED CONSTRUCTION" ELEVATION | | | CERTIFICATE. THIS MUST BE A SIGNED, SEALED DATED | | | ORIGINAL. PLEASE SUBMIT FOR REVIEW PRIOR TO FINAL | | | INSPECTION. | | | | | | 3. PRIOR TO FINAL INSPECTION, EITHER SUBMIT ENGINEERING | | | FOR THE ENGINEERED FLOOD OPENINGS OR SHOW COMPLIANCE | | | WITH NFIP REQUIREMENTS. | | | | | | 4. RESOLVE ALL EXPIRED PERMIT FOR THIS ADDRESS PRIOR TO | | | FINAL INSPECTION. | | | | | | | | | |
|