Plan Review Notes
Plan Review Notes For Permit 10110644
Permit Number 10110644
Review Stop M
Sequence Number 3
Notes
Date Text
2011-02-02 07:48:37****PROVISOS****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OWNER, CONTRACTOR AND ARCHITECT UNDERSTAND AND
 ACKNOWLEDGE RESPONSIBILITY TO COMPLY WITH ALL OF FEMA'S
 NFIP REQUIREMENTS, CFR TITLE 44, PART 60, FOR NEW
 CONSTRUCTION (PROJECT IS A SUBSTANTIAL IMPROVEMENT).
  
 2. FBC R M1401.5, SUBMIT A "CONSTRUCTION DRAWINGS"
 ELEVATION CERTIFICATE WHICH INCLUDES THE FOLLOWING
 INFORMATION:
  
 PROPOSED ELEVATION FOR MECHANICAL EQUIPMENT, MINIMUM
 7.5'
  
 CLARIFICATION REGARDING LOWEST FLOOR (CAN BE INCLUDED
 IN "COMMENTS" SECTION) IN ORDER TO SHOW COMPLIANCE WITH
 REQUIREMENT THAT DUCTWORK IS INSTALLED ABOVE 7.5'; 6.7
 IS SHOWN ON C2A BUT THAT ELEVATION IS NOT ON THE SURVEY
 (7.63 SHOWN AS CRAWLSPACE ELEVATION).
  
  
 3. REVISE PLAN TO INCORPORATE THE NEW MECHANICAL
 DUCTWORK INSTALLATION DETAIL (DUCTWORK INSTALLED ABOVE
 7'6").
  
 4. FBC R 1411.3.1, PER ARCHITECT, DRAIN FROM AUXILIARY
 DRAIN PAN TO BE REDIRECTED OR REMOVED, REVISE DETAIL
 "SUSPENDED AIR HANDLERS," SHEET M1.
  
 5. PER ARCHITECT, DUCTWORK UNDER HOUSE WILL BE LINED,
 FBC R 1601.1.2, 1601.3.10. INCORPORATE REQUIREMENT INTO
 PLAN.
  
  