| 2011-02-02 07:48:37 | ****PROVISOS**** |
| | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | HAROLD MOSER, MECHANICAL PLANS EXAMINER |
| | 561-805-6732 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. OWNER, CONTRACTOR AND ARCHITECT UNDERSTAND AND |
| | ACKNOWLEDGE RESPONSIBILITY TO COMPLY WITH ALL OF FEMA'S |
| | NFIP REQUIREMENTS, CFR TITLE 44, PART 60, FOR NEW |
| | CONSTRUCTION (PROJECT IS A SUBSTANTIAL IMPROVEMENT). |
| | |
| | 2. FBC R M1401.5, SUBMIT A "CONSTRUCTION DRAWINGS" |
| | ELEVATION CERTIFICATE WHICH INCLUDES THE FOLLOWING |
| | INFORMATION: |
| | |
| | PROPOSED ELEVATION FOR MECHANICAL EQUIPMENT, MINIMUM |
| | 7.5' |
| | |
| | CLARIFICATION REGARDING LOWEST FLOOR (CAN BE INCLUDED |
| | IN "COMMENTS" SECTION) IN ORDER TO SHOW COMPLIANCE WITH |
| | REQUIREMENT THAT DUCTWORK IS INSTALLED ABOVE 7.5'; 6.7 |
| | IS SHOWN ON C2A BUT THAT ELEVATION IS NOT ON THE SURVEY |
| | (7.63 SHOWN AS CRAWLSPACE ELEVATION). |
| | |
| | |
| | 3. REVISE PLAN TO INCORPORATE THE NEW MECHANICAL |
| | DUCTWORK INSTALLATION DETAIL (DUCTWORK INSTALLED ABOVE |
| | 7'6"). |
| | |
| | 4. FBC R 1411.3.1, PER ARCHITECT, DRAIN FROM AUXILIARY |
| | DRAIN PAN TO BE REDIRECTED OR REMOVED, REVISE DETAIL |
| | "SUSPENDED AIR HANDLERS," SHEET M1. |
| | |
| | 5. PER ARCHITECT, DUCTWORK UNDER HOUSE WILL BE LINED, |
| | FBC R 1601.1.2, 1601.3.10. INCORPORATE REQUIREMENT INTO |
| | PLAN. |
| | |
| | |