Plan Review Notes
Plan Review Notes For Permit 10110644
Permit Number 10110644
Review Stop B
Sequence Number 3
Notes
Date Text
2011-02-02 08:04:08PERMIT NOT TO BE ISSUED PER JORGE ALVA, P.E. UNTIL HE
 HAS HAD AN OPPORTUNITY TO REVIEW PLANS, COMMENTS, AND
 POSSIBLE PROVISO ITEMS
  
  
 ****PROVISOS****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
  
 1. OWNER, CONTRACTOR, AND ARCHITECT UNDERSTAND AND
 ACKNOWLEDGE RESPONSIBILITY TO COMPLY WITH ALL OF FEMA'S
 NFIP REQUIREMENTS, CFR TITLE 44, PART 60, FOR NEW
 CONSTRUCTION (PROJECT IS SUBSTANTIAL IMPROVEMENT).
  
 2. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS
 DOOR, EXTERIOR DOORS, FAC9B72. SUBMIT AS A REVISION
 PRIOR TO INSTALLATION.
  
 2. FLOOD OPENINGS IN COMPLIANCE WITH NFIP REQUIREMENTS
 REQUIRED. SUBMIT A DETAIL AND A REVISED ELEVATION
 CERTIFICATE SHOWING COMPLIANCE.
  
 HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORD
 S/SI.SHTM
 HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1579
  
 3. INCLUDE WALKWAY BETWEEN GARAGE AND HOUSE ELEVATION
 ON THE SURVEY, MINIMUM 7'6" REQUIRED.
  
 4. SUBMIT A "CONSTRUCTION DRAWINGS" ELEVATION
 CERTIFICATE REVISED AS FOLLOWS:
  
 A. SEE A8 ON ELEVATION CERTIFICATE. PRIOR TO FINAL
 INSPECTION, A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE WHICH SHOWS COMPLIANCE WITH NFIP
 REQUIREMENTS IS REQUIRED. PROVIDE A DETAIL TO SHOW HOW
 COMPLIANCE IS PROPOSED.
  
 B. THE ELEVATION CERTIFICATE PROVIDED AT PERMIT
 APPLICATION IS FOR "FINISHED CONSTRUCTION." AS NEW
 CONSTRUCTION IS PROPOSED (NEW MECHANICAL EQUIPMENT AND
 SLAB, SUBSTANTIAL IMPROVEMENT), THREE ELEVATION
 CERTIFICATES WILL BE REQUIRED FOR THE RENOVATION;
 CONSTRUCTION DRAWINGS, BUILDING UNDER CONSTRUCTION, AND
 FINISHED CONSTRUCTION. PLEASE PROVIDE A REVISED
 ELEVATION CERTIFICATE, "CONSTRUCTION DRAWINGS."
  
 C. SEE INSTRUCTIONS, A5, WHEN LATITUDE AND LONGITUDE
 ARE PROVIDED BY A SURVEYOR, PROVIDE METHOD USED IN
 COMMENTS.
  
 D. ORIGINAL SIGNED AND SEALED DOCUMENTS REQUIRED, SEE
 ELEVATION CERTIFICATE INSTRUCTIONS.
  
 E. SEE C2 A, 6.7 FEET IS STATED AS "TOP OF BOTTOM FLOOR
 (INCLUDING BASEMENT, CRAWLSPACE, OR ENCLOSURE FLOOR)."
 I WAS UNABLE TO LOCATE THIS ELEVATION ON THE SURVEY.
 THIS ELEVATION CONFLICTS WITH ARCHITECT'S DETAIL FOR
 MECHANICAL DUCTWORK. IF NECESSARY, USE THE COMMENTS
 SECTION TO CLARIFY AND TO SHOW COMPLIANCE WITH NFIP
 REQUIREMENTS. OWNER AND ARCHITECT ACKNOWLEDGE
 RESPONSIBILITY FOR FLOOR (INCLUDING BOTTOM OF JOISTS)
 AND MECHANICAL EQUIPMENT (INCLUDING DUCTWORK) TO BE
 ABOVE 7'6". A REVISED ELEVATION CERTIFICATE TO BE
 SUBMITTED.
  
 4. INCORPORATE THE DETAIL FOR DUCTWORK INTO THE PLAN.
 NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN. PROPOSED
 ELEVATION IS TO BE INCLUDED ON THE ELEVATION
 CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B).
 SEE ALSO
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS. MECHANICAL PLAN TO BE SUBMITTED
 EITHER WITH THE MECHANICAL APPLICATION OR AS A
 REVISION.
  
 5. UNDER STAIR STORAGE IS SHOWN. SHOW COMPLIANCE WITH
 FBC R311.2.2., UNDER STAIR PROTECTION (UNDERSIDE OF
 STAIR/CEILING OF STORAGE AREA). REVISE DETAIL.
  
 6. PLEASE RESOLVE EXPIRED PERMITS ON THIS ADDRESS PRIOR
 TO JOB COMPLETION.
  
  
  
  
  