Plan Review Notes
Plan Review Notes For Permit 10110644
Permit Number 10110644
Review Stop M
Sequence Number 2
Notes
Date Text
2011-01-28 11:07:08****CORRECTIONS****
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC R M1401.5, THIS PARCEL IS LOCATED IN A HIGH
 HAZARD FLOOD ZONE. BASED ON THE VALUE, THIS IMPROVEMENT
 IS A SUBSTANTIAL IMPROVEMENT, SEE MUNICIPAL CODE
 94-546(B). PLEASE REVISE PLAN TO SHOW PROPOSED
 ELEVATION OF NEW EQUIPMENT AND INCLUDE PROPOSED
 ELEVATION OF MECHANICAL EQUIPMENT ON THE ELEVATION
 CERTIFICATE.
  
 2ND REVIEW, ELEVATION CERTIFICATE DOES NOT CORRELATE
 WITH PLANS AND ARCHITECT'S INFORMATION. SEE BUILDING
 COMMENTS. ELEVATION CERTIFICATE AT CONSTRUCTION
 DOCUMENT PHASE IS TO INCLUDE PROPOSED ELEVATION FOR NEW
 EQUIPMENT AND FOR DUCTWORK. DETAIL SHOWING THAT
 DUCTWORK TO BE INSTALLED ABOVE 7.5' TO BE INCORPORATED
 INTO THE PLAN.
  
 2. NEW DUCTWORK IN THE CRAWL SPACE IS SHOWN. SEE
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS.
  
 2ND REVIEW, SEE COMMENT #1.
  
 3-5. ADDRESSED.
  
 6. FBC R 1307.3, MECHANICAL EQUIPMENT TO BE DESIGNED TO
 RESIST SLIDING AND OVERTURNING, NOT CLEAR IF THE
 ANCHORS SPECIFIED FOR UPLIFT MEET THIS REQUIREMENT.
 HAVE ENGINEER INCLUDE THIS CRITERIA WITH THE UPLIFT
 STATEMENT.
  
 2ND REVIEW, NO ANCHORS SPECIFIED FOR BOTTOM OF STAND.
  
 7. ADDRESSED.
  
 8. FBC R 1411.3.1, PLAN SHOWS A DRAIN FROM AUXILIARY
 DRAIN PAN TO CONDENSATE DRAIN LINE. THIS DESIGN DOES
 NOT COMPLY WITH THE OPTIONS IN THE CODE, PLEASE REVISE.
  
 2ND REVIEW, FLOAT SWITCH IS NOTED. HOWEVER, THE DRAIN
 LINE FROM THE AUXILIAIRY DRAIN PAN TO CONDENSATE DRAIN
 LINE IS NOT PERMITTED. PLEASE REMOVE OR REROUTE AS PER
 FBC R1411.3.
  
 9. DUCT UNDER HOUSE TO BE LINED, FBC R 1601.1.2,
 1601.3.10. REVISE PLAN TO SHOW COMPLIANCE.
  
 2ND REVIEW, DUCT IS NOTED AS INSULATED. PLEASE INCLUDE
 REQUIREMENT THAT DUCT IS TO BE LINED (INSIDE OF DUCT)
 FOR UNDER HOUSE DUCTWORK.
  
  