| 2011-01-28 11:07:08 | ****CORRECTIONS**** |
| | HAROLD MOSER, MECHANICAL PLANS EXAMINER |
| | 561-805-6732 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. FBC R M1401.5, THIS PARCEL IS LOCATED IN A HIGH |
| | HAZARD FLOOD ZONE. BASED ON THE VALUE, THIS IMPROVEMENT |
| | IS A SUBSTANTIAL IMPROVEMENT, SEE MUNICIPAL CODE |
| | 94-546(B). PLEASE REVISE PLAN TO SHOW PROPOSED |
| | ELEVATION OF NEW EQUIPMENT AND INCLUDE PROPOSED |
| | ELEVATION OF MECHANICAL EQUIPMENT ON THE ELEVATION |
| | CERTIFICATE. |
| | |
| | 2ND REVIEW, ELEVATION CERTIFICATE DOES NOT CORRELATE |
| | WITH PLANS AND ARCHITECT'S INFORMATION. SEE BUILDING |
| | COMMENTS. ELEVATION CERTIFICATE AT CONSTRUCTION |
| | DOCUMENT PHASE IS TO INCLUDE PROPOSED ELEVATION FOR NEW |
| | EQUIPMENT AND FOR DUCTWORK. DETAIL SHOWING THAT |
| | DUCTWORK TO BE INSTALLED ABOVE 7.5' TO BE INCORPORATED |
| | INTO THE PLAN. |
| | |
| | 2. NEW DUCTWORK IN THE CRAWL SPACE IS SHOWN. SEE |
| | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR |
| | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL |
| | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH |
| | NFIP REQUIREMENTS. |
| | |
| | 2ND REVIEW, SEE COMMENT #1. |
| | |
| | 3-5. ADDRESSED. |
| | |
| | 6. FBC R 1307.3, MECHANICAL EQUIPMENT TO BE DESIGNED TO |
| | RESIST SLIDING AND OVERTURNING, NOT CLEAR IF THE |
| | ANCHORS SPECIFIED FOR UPLIFT MEET THIS REQUIREMENT. |
| | HAVE ENGINEER INCLUDE THIS CRITERIA WITH THE UPLIFT |
| | STATEMENT. |
| | |
| | 2ND REVIEW, NO ANCHORS SPECIFIED FOR BOTTOM OF STAND. |
| | |
| | 7. ADDRESSED. |
| | |
| | 8. FBC R 1411.3.1, PLAN SHOWS A DRAIN FROM AUXILIARY |
| | DRAIN PAN TO CONDENSATE DRAIN LINE. THIS DESIGN DOES |
| | NOT COMPLY WITH THE OPTIONS IN THE CODE, PLEASE REVISE. |
| | |
| | 2ND REVIEW, FLOAT SWITCH IS NOTED. HOWEVER, THE DRAIN |
| | LINE FROM THE AUXILIAIRY DRAIN PAN TO CONDENSATE DRAIN |
| | LINE IS NOT PERMITTED. PLEASE REMOVE OR REROUTE AS PER |
| | FBC R1411.3. |
| | |
| | 9. DUCT UNDER HOUSE TO BE LINED, FBC R 1601.1.2, |
| | 1601.3.10. REVISE PLAN TO SHOW COMPLIANCE. |
| | |
| | 2ND REVIEW, DUCT IS NOTED AS INSULATED. PLEASE INCLUDE |
| | REQUIREMENT THAT DUCT IS TO BE LINED (INSIDE OF DUCT) |
| | FOR UNDER HOUSE DUCTWORK. |
| | |
| | |