| Date |
Text |
| 2011-01-27 14:06:02 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PROVIDE PRODUCT APPROVALS REQUIRED FOR SLIDING GLASS |
| | DOOR, EXTERIOR DOORS, FAC9B72. |
| | |
| | 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP |
| | DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN |
| | /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH NFIP |
| | REQUIREMENTS IS REQUIRED. BASED ON THE ELEVATION |
| | CERTIFICATE PROVIDED, FLOOD OPENINGS, ITEM A8 ON |
| | ELEVATION CERTIFICATE, DO NOT COMPLY WITH NFIP |
| | REQUIREMENTS. SEE THE FEMA WEBSITE FOR MORE INFORMATION |
| | REGARDING REQUIREMENTS AND COMPLIANCE: |
| | |
| | HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORD |
| | S/SI.SHTM |
| | HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1579 |
| | |
| | ALSO SEE THE WALKWAY BETWEEN THE GARAGE AND MAIN HOUSE. |
| | THIS APPEARS TO BE HABITABLE SPACE (SHOWS WINDOWS, |
| | ROOF, FLOOR). SHOW THAT THIS AREA MEETS THE NFIP |
| | REQUIREMENTS (MINIMUM 7'6"). |
| | |
| | 3. THE FOLLOWING COMMENTS PERTAIN TO THE ELEVATION |
| | CERTIFICATE PROVIDED. PLEASE ALSO SEE ELEVATION |
| | CERTIFICATE INSTRUCTIONS, |
| | HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1383. |
| | |
| | A. SEE COMMENT #2 REGARDING FLOOD OPENINGS, A8 ON |
| | ELEVATION CERTIFICATE. PRIOR TO FINAL INSPECTION, A |
| | "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WHICH |
| | SHOWS COMPLIANCE WITH NFIP REQUIREMENTS IS REQUIRED. |
| | |
| | B. THE ELEVATION CERTIFICATE PROVIDED IS FOR "FINISHED |
| | CONSTRUCTION." AS NEW CONSTRUCTION IS PROPOSED (NEW |
| | MECHANICAL EQUIPMENT AND SLAB, SUBSTANTIAL |
| | IMPROVEMENT), THREE ELEVATION CERTIFICATES WILL BE |
| | REQUIRED FOR THE RENOVATION; CONSTRUCTION DRAWINGS, |
| | BUILDING UNDER CONSTRUCTION, AND FINISHED CONSTRUCTION. |
| | PLEASE PROVIDE A REVISED ELEVATION CERTIFICATE, |
| | "CONSTRUCTION DRAWINGS." |
| | |
| | C. SEE INSTRUCTIONS, A5, WHEN LATITUDE AND LONGITUDE |
| | ARE PROVIDED BY A SURVEYOR, PROVIDE METHOD USED IN |
| | COMMENTS. |
| | |
| | D. ORIGINAL SIGNED AND SEALED DOCUMENTS REQUIRED, SEE |
| | ELEVATION CERTIFICATE INSTRUCTIONS. |
| | |
| | E. SEE C2 A, 6.7 FEET IS STATED AS "TOP OF BOTTOM FLOOR |
| | (INCLUDING BASEMENT, CRAWLSPACE, OR ENCLOSURE FLOOR)." |
| | I WAS UNABLE TO LOCATE THIS ELEVATION ON THE SURVEY. |
| | THIS ELEVATION CONFLICTS WITH ARCHITECT'S DETAIL FOR |
| | MECHANICAL DUCTWORK. IF NECESSARY, USE THE COMMENTS |
| | SECTION TO CLARIFY AND TO SHOW COMPLIANCE WITH NFIP |
| | REQUIREMENTS. |
| | |
| | 4. INCORPORATE THE DETAIL FOR DUCTWORK INTO THE PLAN. |
| | NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN. PROPOSED |
| | ELEVATION IS TO BE INCLUDED ON THE ELEVATION |
| | CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B). |
| | SEE ALSO |
| | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR |
| | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL |
| | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH |
| | NFIP REQUIREMENTS. |
| | |
| | 5. UNDER STAIR STORAGE IS SHOWN. SHOW COMPLIANCE WITH |
| | FBC R311.2.2., UNDER STAIR PROTECTION (UNDERSIDE OF |
| | STAIR/CEILING OF STORAGE AREA). |
| | |
| | 6. SEE IMPACT FEE COMMENTS. 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | |