1 |
|
| Notes |
| Date |
Text |
| 2010-12-17 10:48:47 | DENIED BY PLUMBING | | | | | | 1) SUBMIT TWO SETS OF SANITARY ISOMETRIC DRAWINGS FOR | | | THE PROJECT AS REQUIRED BY FBC 106.3.5.4. SPECIFY THE | | | PIPE SIZES, CLEAN OUTS, TRAPS, FIXTURE TYPES, ETC. | | | | | | 2) THE PLUMBING PLAN ON PL-1 SHOWS THE 4" BUILDING | | | DRAIN TYING INTO A NEW 3" BUILDING DRAIN AT THE PANTRY | | | AREA AND CONTINUING TO AN EXISTING 3" BUILDING SEWER. | | | FBC R 3005.1.7 DOES NOT ALLOW THE SIZE OF THE DRAINAGE | | | PIPING TO BE REDUCED IN SIZE IN THE DIRECTION OF THE | | | FLOW. PLEASE CORRECT. | | | | | | 3) THE PLUMBING FIXTURE SCHEDULE ON PL-1 CONTAINS | | | NUMEROUS ERRORS. THE TRAP SIZES ARE INCORRECT. SEE FBCR | | | TABLE P3201.7. THE SHOWERS ARE MARKED P3, THE SINKS ARE | | | MARKED P4 ON THE PLANS AND THE SCHEDULE DOES NOT | | | CORRESPOND. PLEASE CORRECT. | | | | | | 4) THE TOTAL FIXTURE UNIT COUNT IS NOT CORRECT. SEE | | | FBCR TABLE P3004.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|