Plan Review Notes
Plan Review Notes For Permit 10110644
Permit Number 10110644
Review Stop M
Sequence Number 1
Notes
Date Text
2011-01-03 09:59:24****CORRECTIONS****
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC R M1401.5, THIS PARCEL IS LOCATED IN A HIGH
 HAZARD FLOOD ZONE. BASED ON THE VALUE, THIS IMPROVEMENT
 IS A SUBSTANTIAL IMPROVEMENT, SEE MUNICIPAL CODE
 94-546(B). PLEASE REVISE PLAN TO SHOW PROPOSED
 ELEVATION OF NEW EQUIPMENT AND INCLUDE PROPOSED
 ELEVATION OF MECHANICAL EQUIPMENT ON THE ELEVATION
 CERTIFICATE.
  
 2. NEW DUCTWORK IN THE CRAWL SPACE IS SHOWN. SEE
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS.
  
 3. FBC 106, THE SITE PLAN HAS A HANDWRITTEN NOTE WHICH
 STATES NOT TO EXCEED 2FT SETBACK. THE BUILDING IS SHOWN
 AT 4.8FT FROM PROPERTY LINE, M1 SHOWS 1FT BETWEEN UNIT
 AND BUILDING AND 34IN DEPTH FOR THE UNIT. PLEASE
 CONFIRM UNIT SIZE AND LOCATION AND DISTANCE TO PROPERTY
 LINE.
  
 5. M1, HVAC GENERAL NOTE 6, R4 DUCTS DO NOT COMPLY WITH
 FBC R TABLE 1110.AB.2.1. THIS APPEARS TO BE A GENERAL
 NOTE NOT APPLICABLE TO DETAILS SPECIFIC TO THIS JOB;
 EITHER REMOVE OR COMPLY.
  
 6. FBC R 1307.3, MECHANICAL EQUIPMENT TO BE DESIGNED TO
 RESIST SLIDING AND OVERTURNING, NOT CLEAR IF THE
 ANCHORS SPECIFIED FOR UPLIFT MEET THIS REQUIREMENT.
 HAVE ENGINEER INCLUDE THIS CRITERIA WITH THE UPLIFT
 STATEMENT.
  
 7. AHU 3 GROUND FLOOR DOOR ENCROACHES ON THE UNIT
 SPACE, DOES NOT APPEAR THAT THE DOOR SHOWN ON M2 CAN
 CLOSE, AND WHAT APPEARS TO BE THE RETURN AIR REGISTER
 IS OUTSIDE THE DOOR. ACCESS TO THE UNIT IS NOT CLEAR.
 ARCHITECTURAL SHEETS ARE NOT CONSISTENT WITH M2 SHEETS
 REGARDING AHU 3 DOOR.
  
 8. FBC R 1411.3.1, PLAN SHOWS A DRAIN FROM AUXILIARY
 DRAIN PAN TO CONDENSATE DRAIN LINE. THIS DESIGN DOES
 NOT COMPLY WITH THE OPTIONS IN THE CODE, PLEASE REVISE.
  
 9. DUCT UNDER HOUSE TO BE LINED, FBC R 1601.1.2,
 1601.3.10. REVISE PLAN TO SHOW COMPLIANCE.
  