| 2011-01-03 09:59:24 | ****CORRECTIONS**** |
| | HAROLD MOSER, MECHANICAL PLANS EXAMINER |
| | 561-805-6732 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. FBC R M1401.5, THIS PARCEL IS LOCATED IN A HIGH |
| | HAZARD FLOOD ZONE. BASED ON THE VALUE, THIS IMPROVEMENT |
| | IS A SUBSTANTIAL IMPROVEMENT, SEE MUNICIPAL CODE |
| | 94-546(B). PLEASE REVISE PLAN TO SHOW PROPOSED |
| | ELEVATION OF NEW EQUIPMENT AND INCLUDE PROPOSED |
| | ELEVATION OF MECHANICAL EQUIPMENT ON THE ELEVATION |
| | CERTIFICATE. |
| | |
| | 2. NEW DUCTWORK IN THE CRAWL SPACE IS SHOWN. SEE |
| | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR |
| | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL |
| | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH |
| | NFIP REQUIREMENTS. |
| | |
| | 3. FBC 106, THE SITE PLAN HAS A HANDWRITTEN NOTE WHICH |
| | STATES NOT TO EXCEED 2FT SETBACK. THE BUILDING IS SHOWN |
| | AT 4.8FT FROM PROPERTY LINE, M1 SHOWS 1FT BETWEEN UNIT |
| | AND BUILDING AND 34IN DEPTH FOR THE UNIT. PLEASE |
| | CONFIRM UNIT SIZE AND LOCATION AND DISTANCE TO PROPERTY |
| | LINE. |
| | |
| | 5. M1, HVAC GENERAL NOTE 6, R4 DUCTS DO NOT COMPLY WITH |
| | FBC R TABLE 1110.AB.2.1. THIS APPEARS TO BE A GENERAL |
| | NOTE NOT APPLICABLE TO DETAILS SPECIFIC TO THIS JOB; |
| | EITHER REMOVE OR COMPLY. |
| | |
| | 6. FBC R 1307.3, MECHANICAL EQUIPMENT TO BE DESIGNED TO |
| | RESIST SLIDING AND OVERTURNING, NOT CLEAR IF THE |
| | ANCHORS SPECIFIED FOR UPLIFT MEET THIS REQUIREMENT. |
| | HAVE ENGINEER INCLUDE THIS CRITERIA WITH THE UPLIFT |
| | STATEMENT. |
| | |
| | 7. AHU 3 GROUND FLOOR DOOR ENCROACHES ON THE UNIT |
| | SPACE, DOES NOT APPEAR THAT THE DOOR SHOWN ON M2 CAN |
| | CLOSE, AND WHAT APPEARS TO BE THE RETURN AIR REGISTER |
| | IS OUTSIDE THE DOOR. ACCESS TO THE UNIT IS NOT CLEAR. |
| | ARCHITECTURAL SHEETS ARE NOT CONSISTENT WITH M2 SHEETS |
| | REGARDING AHU 3 DOOR. |
| | |
| | 8. FBC R 1411.3.1, PLAN SHOWS A DRAIN FROM AUXILIARY |
| | DRAIN PAN TO CONDENSATE DRAIN LINE. THIS DESIGN DOES |
| | NOT COMPLY WITH THE OPTIONS IN THE CODE, PLEASE REVISE. |
| | |
| | 9. DUCT UNDER HOUSE TO BE LINED, FBC R 1601.1.2, |
| | 1601.3.10. REVISE PLAN TO SHOW COMPLIANCE. |
| | |