Plan Review Notes
Plan Review Notes For Permit 10110644
Permit Number 10110644
Review Stop B
Sequence Number 1
Notes
Date Text
2010-12-07 11:33:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PRODUCT APPROVALS REQUIRED FOR COMPONENTS & CLADDING
 (DOORS, WINDOWS, MULLIONS), FAC9B72. PRODUCT APPROVALS
 ARE TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL.
  
 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP
 DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN
 /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH ALL REQUIREMENTS
 TO BE SHOWN ON THE PLAN. SEE ALSO CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B). NOTE THAT THIS
 STRUCTURE IS LOCATED IN THE A5 FLOOD ZONE, 7'6" MINIMUM
 ELEVATION REQUIRED. PLEASE REFER TO FEMA WEBSITE FOR
 FURTHER GUIDANCE. PLEASE FEEL FREE TO CONTACT ME FOR
 FURTHER ASSISTANCE.
  
 3. PROVIDE AN ELEVATION CERTIFICATE; HTTP://WWW.FEMA.GO
 V/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORDS/SI.SHTM.
  
 4. NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN.
 PROPOSED ELEVATION IS TO BE INCLUDED ON THE ELEVATION
 CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B).
 SEE ALSO
 HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR
 REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL
 DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH
 NFIP REQUIREMENTS.
  
 5. REVISE SITE PLAN TO SHOW LOCATION OF MECHANICAL
 EQUIPMENT RELATIVE TO THE PROPERTY LINE, FBC106.
  
 6. DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING
 401.4.
  
 7. DECLARE WIND DESIGN CRITERIA FBC 1603.1.4, FBC R301.
  
 8. IMPACT PROTECTION REQUIRED FOR GLAZING, FBC R
 301.2.1.2. IF SHUTTERS ARE PROPOSED, THE FOLLOWING
 INFORMATION WILL BE REQUIRED:
  
 A. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_F
 OR_INSTALLATION.PDF
  
 B. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 C. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
 9. IT APPEARS THAT UNDER STAIR STORAGE IS SHOWN. SHOW
 COMPLIANCE WITH FBC R311.2.2., UNDER STAIR PROTECTION.
  
 10. SEE IMPACT FEE COMMENTS. 233-5025 FOR MORE
 INFORMATION.
  
  
  