| 2010-12-07 11:33:50 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PRODUCT APPROVALS REQUIRED FOR COMPONENTS & CLADDING |
| | (DOORS, WINDOWS, MULLIONS), FAC9B72. PRODUCT APPROVALS |
| | ARE TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL. |
| | |
| | 2. THIS IS A SUBSTANTIAL IMPROVEMENT, SEE FEMA NFIP |
| | DEFINITION, HTTP://WWW.FEMA.GOV/PLAN/PREVENT/FLOODPLAIN |
| | /NFIPKEYWORDS/SI.SHTM. COMPLIANCE WITH ALL REQUIREMENTS |
| | TO BE SHOWN ON THE PLAN. SEE ALSO CITY OF WEST PALM |
| | BEACH MUNICIPAL CODE 94-546(B). NOTE THAT THIS |
| | STRUCTURE IS LOCATED IN THE A5 FLOOD ZONE, 7'6" MINIMUM |
| | ELEVATION REQUIRED. PLEASE REFER TO FEMA WEBSITE FOR |
| | FURTHER GUIDANCE. PLEASE FEEL FREE TO CONTACT ME FOR |
| | FURTHER ASSISTANCE. |
| | |
| | 3. PROVIDE AN ELEVATION CERTIFICATE; HTTP://WWW.FEMA.GO |
| | V/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORDS/SI.SHTM. |
| | |
| | 4. NEW MECHANICAL EQUIPMENT AND DUCTWORK SHOWN. |
| | PROPOSED ELEVATION IS TO BE INCLUDED ON THE ELEVATION |
| | CERTIFICATE AND ON THE PLAN, MUNICIPAL CODE 94-546(B). |
| | SEE ALSO |
| | HTTP://WWW.FEMA.GOV/PDF/FIMA/PBUFFD_CHAPTER_3.PDF FOR |
| | REQUIREMENTS FOR HVAC SYSTEMS. PLEASE REVISE MECHANICAL |
| | DETAILS TO INCLUDE ELEVATIONS TO SHOW COMPLIANCE WITH |
| | NFIP REQUIREMENTS. |
| | |
| | 5. REVISE SITE PLAN TO SHOW LOCATION OF MECHANICAL |
| | EQUIPMENT RELATIVE TO THE PROPERTY LINE, FBC106. |
| | |
| | 6. DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING |
| | 401.4. |
| | |
| | 7. DECLARE WIND DESIGN CRITERIA FBC 1603.1.4, FBC R301. |
| | |
| | 8. IMPACT PROTECTION REQUIRED FOR GLAZING, FBC R |
| | 301.2.1.2. IF SHUTTERS ARE PROPOSED, THE FOLLOWING |
| | INFORMATION WILL BE REQUIRED: |
| | |
| | A. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_F |
| | OR_INSTALLATION.PDF |
| | |
| | B. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL |
| | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE |
| | INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609, |
| | FBC*106. |
| | |
| | C. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. |
| | |
| | 9. IT APPEARS THAT UNDER STAIR STORAGE IS SHOWN. SHOW |
| | COMPLIANCE WITH FBC R311.2.2., UNDER STAIR PROTECTION. |
| | |
| | 10. SEE IMPACT FEE COMMENTS. 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | |