| Plan Review Notes For Permit 10110630 |
| Permit Number |
10110630 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-30 17:34:31 | ELECTRIC PLAN REVIEW FAIL | | | 1) 4-600 AND 1- 500 MCM THHN CONDUCTORS DO NOT FIT INTO | | | A 3 1/2 PVC CONDUIT | | | | | | | | | JOHN DICKINSON | | | CONTRACT PLAN REVIEWER | | | CELL 561-718-3230 |
|