2010-12-06 10:22:26295 LAKEVIEW AVENUE
 PERMIT NUMBER 10110605
 "ADD SERVICE BAR IN HOTEL LOBBY. TIE INTO EXISTING
 ELECTRICAL AND PLUMBING"
  
 1. INFORMATION IN THE PROJECT DATA BOX IS INCORRECT.
 THE EXISTING BUILDING IS A HOTEL AND NOT A BUSINESS
 OCCUPANCY.
  
 2. THE PROJECT DATA BOX INDICATES IT IS ONLY A FOUR
 STORY BUILDING. THE BUILDING CONTAINS MORE THAN FOUR
 FLOORS.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER OR FIRE ALARM SYSTEM REMODELING.
  
 4. THE PLANS INDICATE THAT THE FLOOR SLAB IS TO BE
 SAWCUT. IF GASOLINE POWERED SAWS ARE TO BE USED
 ADEQUATE VENTILATION CONTROLS ARE TO BE PROVIDED SO NO
 BUILD-UP OF CARBON MONOXIDE (CO) OCCURS. CARBON
 MONOXIDE IS A COLORLESS AND ODORLESS GAS THAT CAN BE
 FLAMMABLE IS THE PROPER CONCENTRATION. NO FLAMMABLE OR
 COMBUSTIBLE LIQUIDS ARE TO BE STORED IN THE BUILDING.
  
 5. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 6. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 7. PLEASE INDICATE HOW CONSTRUCTION FROM
 NON-CONSTRUCTION AREAS ARE TO BE SEPARATED AS IT IS
 ASSUMED THAT THE HOTEL WILL REMAIN OPEN DURING WORK
 PERIODS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION