| | BUILDING PLAN REVIEW |
| | PERMIT: 10110584 |
| | ADD: 222 LAKEVIEW AVE/ 14TH FLOOR |
| | CONT: ROYAL ASSET SECURITY INC |
| | TEL: (561)504-5800 |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1008.1.3.4 ACCESS-CONTROLLED EGRESS DOORS |
| | |
| | BUILDING PROVISO: |
| | |
| | 1008.1.3.4 ACCESS-CONTROLLED EGRESS DOORS. THE ENTRANCE |
| | DOORS IN A MEANS OF EGRESS IN BUILDINGS WITH AN |
| | OCCUPANCY IN GROUP A, B, D, E, M, R-1 OR R-2 AND |
| | ENTRANCE DOORS TO TENANT SPACES IN OCCUPANCIES IN |
| | GROUPS A, B, D, E, M, R-1 AND R-2 ARE PERMITTED TO BE |
| | EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS |
| | CONTROL SYSTEM WHICH SHALL BE INSTALLED IN ACCORDANCE |
| | WITH ALL OF THE FOLLOWING CRITERIA: |
| | |
| | 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE |
| | ARRANGED TO DETECT AN OCCUPANT APPROACHING THE DOORS. |
| | THE DOORS SHALL BE ARRANGED TO UNLOCK BY A SIGNAL FROM |
| | OR LOSS OF POWER TO THE SENSOR. |
| | |
| | 2. LOSS OF POWER TO THAT PART OF THE ACCESS CONTROL |
| | SYSTEM WHICH LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| | THE DOORS. |
| | |
| | 3. THE DOORS SHALL BE ARRANGED TO UNLOCK FROM A MANUAL |
| | UNLOCKING DEVICE LOCATED 40 INCHES TO 48 INCHES (1016 |
| | MM TO 1219 MM) VERTICALLY ABOVE THE FLOOR AND WITHIN 5 |
| | FEET (1524 MM) OF THE SECURED DOORS. READY ACCESS SHALL |
| | BE PROVIDED TO THE MANUAL UNLOCKING DEVICE AND THE |
| | DEVICE SHALL BE CLEARLY IDENTIFIED BY A SIGN THAT READS |
| | "PUSH TO EXIT." WHEN OPERATED, THE MANUAL UNLOCKING |
| | DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF POWER TO |
| | THE LOCK???INDEPENDENT OF THE ACCESS CONTROL SYSTEM |
| | ELECTRONICS???AND THE DOORS SHALL REMAIN UNLOCKED FOR A |
| | MINIMUM OF 30 SECONDS. |
| | |
| | 4. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM, IF |
| | PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOORS, AND THE |
| | DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM |
| | HAS BEEN RESET. |
| | |
| | 5. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR |
| | FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY |
| | UNLOCK THE DOORS. THE DOORS SHALL REMAIN UNLOCKED UNTIL |
| | THE FIRE ALARM SYSTEM HAS BEEN RESET. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |