| 2010-11-23 10:41:08 | 505 SOUTH FLAGLER DRIVE, SUITE #700 | | | PERMIT #10110567 | | | MASTER #10080742 | | | REVIEW COMMENTS - FIRE | | | | | | | | | PLANS AND PERMIT APPLICATION SHOW CONFLICTING SUITE | | | NUMBERS (505 AND 700). | | | | | | ACCESS-CONTROLLED EGRESS DOES NOT ALLOW FREE EGRESS | | | FROM THE ELEVATOR LOBBY TO BOTH STAIR EXITS. TWO EXITS | | | ARE REQUIRED PER SECTION 38.2.4.1(3) OF NFPA 101 | | | (FLORIDA FIRE PREVENTION CODE 2007 EDITION). | | | | | | PLEASE DESCRIBE WHAT ACCESS-CONTROL IS INTENDED FOR THE | | | STAIR LOCATED ADJACENT TO THE CONFERENCE ROOM. | | | | | | PLEASE PROVIDE EXITING AND FLOOR PLAN INFORMATION FOR | | | THE 8TH FLOOR KEYPAD INSTALLATION. | | | | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|