 REVIEW COMMENTS - FIRE
  
  
 PLANS AND PERMIT APPLICATION SHOW CONFLICTING SUITE
 NUMBERS (505 AND 700).
  
 ACCESS-CONTROLLED EGRESS DOES NOT ALLOW FREE EGRESS
 FROM THE ELEVATOR LOBBY TO BOTH STAIR EXITS. TWO EXITS
 ARE REQUIRED PER SECTION 38.2.4.1(3) OF NFPA 101
 (FLORIDA FIRE PREVENTION CODE 2007 EDITION).
  
 PLEASE DESCRIBE WHAT ACCESS-CONTROL IS INTENDED FOR THE
 STAIR LOCATED ADJACENT TO THE CONFERENCE ROOM.
  
 PLEASE PROVIDE EXITING AND FLOOR PLAN INFORMATION FOR
 THE 8TH FLOOR KEYPAD INSTALLATION.
  
  