| Plan Review Notes For Permit 10110532 |
| Permit Number |
10110532 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-30 11:06:12 | | | | BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC | | | 210.12 | | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94 | | | THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2 | | | TAMPER -RESISTANCE RECEPTACLES REQUIRED. NEC 406.11, | | | 210.52 | | | MAXIMUM MAIN BREAKER FOR A RESIDENTIAL SERVICE USING | | | 2/0 COPPER CONDUCTORS IS 200 AMPERES. NEC TABLE 310.15 | | | DEDICATED GENERAL PURPOSE GFCI RECEPTACLE REQUIRED IN | | | THE LAUNDRY ROOM. NEC 210. | | | EACH BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210-11(C)(3) | | | LAUNDRY AREA REQUIRES A RECEPTACLE NEC 210.52 (F) | | | DRYER BRANCH CIRCUIT APPEARS UNDERSIZED. | | | INSTA-HOT POWER USAGE INCORRECTLY LISTED. WIRE SIZES | | | ARE INCORRECT. | | | GFCI PROTECTED OUTLETS ARE REQUIRED FRONT AND BACK AT | | | EACH RESIDENTIAL BUILDING AND AT THE LOCATION OF THE | | | MECHANICAL EQUIPMENT . NEC 210-52 (E) (1), 210-63. | | | INDICATE THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR | | | AND ALL GROUNDING ELECTRODES FOR ALL BUILDINGS. NEC | | | 250- 52 | | | RECEPTACLE SPACING IN SEVERAL AREAS REQUIRES | | | CORRECTION. NEC 210.52(A)(1) | | | CARBON MONOXIDE DETECTORS REQUIRED F.S. 553.885 | | | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 | | | |
|