| Plan Review Notes For Permit 10110512 |
| Permit Number |
10110512 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-03 11:35:53 | 1. APPLICANT FAILED TO PROVIDE AN ENGINEER OF RECORD AS | | | PREVIOUSLY REQUESTED IN ACCORDANCE WITH FBC SECTION | | | 105.3.1.2. PROPOSED CHANGES TO THE ELECTRICAL SYSTEM | | | MUST BE SIGNED AND SEALED. | | | 2. THE NEW METER CAN AND DISCONNECT MUST BE PRECISELY | | | LOCATED ON THE PLANS TO SCALE OR DIMENSIONED. | | | 3. VERIFY THE NEW ELECTRICAL X-RAY EQUIPMENT AND | | | CONTROLLERS ARE LISTED BY A NATIONALLY RECOGNIZED | | | TESTING AGENCY. | | | 4. PROVIDE DETAIL FOR THE EQUIPMENT TRANSFORMER | | | INCLUDING CONNECTION SCHEMATIC WITH APPROPRIATE | | | CIRCUITRY DETAIL. | | | 5. PROVIDE A GROUNDING DETAIL FOR THE NEW SERVICE. NEC | | | 2008 SECTION 250-24 | | | | | | R. LECKY, ELECTRICAL PLANS EXAMINER, WPB CONSTRUCTION | | | SERVICES . PHONE 561-805-6718 |
|