2010-12-06 11:47:10411-7TH STREET
 PERMIT NUMBER 10110508
 "ADDITION OF BUILDING TO EXISTING STORAGE FACILITY"
  
  
 1. THE BUILDING ADDRESS IS REQUIRED. THE MINIMUM OF 6"
 HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED ON THE
 PROPER ELEVATION.
  
 2. THE PORTABLE FIRE EXTINGUISHERS ARE TO BE PROPERLY
 SERVICE TAGGED.
  
 3. A MALTESE CROSS IS REQUIRED TO BE PLACED ON THE
 BUILDING WITH THE LETTER R SIGNIFYING THAT A ROOF TRUSS
 EXISTS ON THE BUILDING. THIS IS FOR FIREFIGHTER SAFETY
 AND NEEDS TO BE CALLED OUT ON THE PLANS.
  
 4. PLEASE ENSURE THAT AN EXISTING KNOX-BOX IS PRESENT
 FOR ENTRY THROUGH THE EXISTING GATES SHOWN ON THE
 PLANS.
  
 5. PLEASE INDICATE ON THE PLANS THE TYPES OF MATERIALS
 THAT WILL BE STORED AT THE LOCATION. NO STORAGE OF ANY
 EXPLOSIVES OR HAZARDOUS MATERIALS, FLAMMABLE GASES OR
 LIQUIDS SHALL OCCUR AT THE LOCATION.
  
 6. TACTILE SIGNAGE REQUIRED AT EXIT LOCATIONS.
  
 7. PLEASE INDICATE HOURS OF OPERATION. NO EXIT SIGNAGE
 OR EMERGENCY LIGHTING SHOWN ON THE PLANS. PLEASE REVIEW
 CHAPTER 42 OF THE LIFE SAFETY CODE (101) FOR STORAGE
 OCCUPANCIES
  
 8. PLEASE INDICATE IF LOW, ORDINARY OR HIGH HAZARD
 MATERIALS WILL BE STORED AT THE LOCATION.
  
 9. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 10. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 11. SUITABLE ACCESS SHALL BE PROVIDED FOR FIRE AND
 PARAMEDICAL EQUIPMENT DURING CONSTRUCTION.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION