| 2010-11-23 14:58:21 | NO ROOFING PRODUCT APPROVALS WERE SUBMITTED/ NO ROOFER |
| | APPLIED ON PERMIT APPLICATION SEPERATE PERMIT, REVIEW |
| | AND ASSOCIATED FEES. |
| | |
| | |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET A-1.0 SECTION A WILL REQUIRE A BOND BREAK. |
| | 1404.2.1 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED |
| | TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL BE |
| | TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER AND |
| | THE WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE |
| | PROVIDED BETWEEN THE WATER RESISTIVE BARRIER AND THE |
| | CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE |
| | FOLLOWING: |
| | 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER OR |
| | 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER |
| | OVER AN APPROVED PLASTIC HOUSE WRAP, OR |
| | 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN |
| | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 2) SHEET S-2.0 DETAIL #8 IS MISSING THE STRAP |
| | CONNECTION BETWEEN THE TRUSS AND DOUBLE BOTTOM PLATE. |
| | |