Plan Review Notes
Plan Review Notes For Permit 10110508
Permit Number 10110508
Review Stop B
Sequence Number 1
Notes
Date Text
2010-11-23 14:58:21NO ROOFING PRODUCT APPROVALS WERE SUBMITTED/ NO ROOFER
 APPLIED ON PERMIT APPLICATION SEPERATE PERMIT, REVIEW
 AND ASSOCIATED FEES.
  
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-1.0 SECTION A WILL REQUIRE A BOND BREAK.
 1404.2.1 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED
 TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL BE
 TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER AND
 THE WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER OR
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 2) SHEET S-2.0 DETAIL #8 IS MISSING THE STRAP
 CONNECTION BETWEEN THE TRUSS AND DOUBLE BOTTOM PLATE.
  
 JIM WITMER C. B. O.