Plan Review Notes
Plan Review Notes For Permit 10110486
Permit Number 10110486
Review Stop P
Sequence Number 1
Notes
Date Text
2010-11-22 14:49:13FBC PLUMBING 2007 REVIEW
 DENIED:
  
 USING P.D.I. CALCULATIONS ADDING A THREE COMPARTMENT
 SINK TO EXISTING WILL REQUIRE 1890 GALLON CAPACITY.
 HAND SINKS ARE NOT REQUIRED TO CONNECT TO THE GREASE
 SYSTEM. EXISTING GREASE TRAP IS 1500 GALLONS. AN UNDER
 SINK GREASE REMOVAL DEVISE CONNECTED TO THE SANITARY
 MAY BE REQUIRED IF THE SINK IS NON-FOOD HANDLING ONLY.
 IF THIS SINK IS FOR FOOD HANDLING, THE GRD WILL NOT BE
 IN THE SAME ROOM. A TRAPZILLA OR EQUAL TYPE INTERCEPTOR
 OUTSIDE UNDERGROUND CONNECTED TO THE SANITARY WOULD BE
 OK IN EITHER CASE.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR