| Notes |
| Date |
Text |
| 2010-11-22 14:49:13 | FBC PLUMBING 2007 REVIEW | | | DENIED: | | | | | | USING P.D.I. CALCULATIONS ADDING A THREE COMPARTMENT | | | SINK TO EXISTING WILL REQUIRE 1890 GALLON CAPACITY. | | | HAND SINKS ARE NOT REQUIRED TO CONNECT TO THE GREASE | | | SYSTEM. EXISTING GREASE TRAP IS 1500 GALLONS. AN UNDER | | | SINK GREASE REMOVAL DEVISE CONNECTED TO THE SANITARY | | | MAY BE REQUIRED IF THE SINK IS NON-FOOD HANDLING ONLY. | | | IF THIS SINK IS FOR FOOD HANDLING, THE GRD WILL NOT BE | | | IN THE SAME ROOM. A TRAPZILLA OR EQUAL TYPE INTERCEPTOR | | | OUTSIDE UNDERGROUND CONNECTED TO THE SANITARY WOULD BE | | | OK IN EITHER CASE. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | |
|