2010-11-23 10:39:12BUILDING PLAN REVIEW
 PERMIT: 10070434/ REV 10110486
 ADD: 600 VILLAGE BLVD
 CONT: 3-D HOMES
 TEL: (561)662-9327
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE ORIGINAL PERMIT WAS FOR A COMMERCIAL REMODEL, NO
 SURVEY WAS REQUIRED, NOW THIS REVISION INDICATES A NEW
 ADDITION, PLEASE SUBMIT A SURVEY INDICATING THE NEW
 ADDITION AND PROPERTY LINE. FBC-B TABLE 600 FOR A TYPE
 IIIB BUILDING BEARING WALLS 2 HOUR RATED WALLS (SEE
 CODE COMMENTARY) , FOOTNOTE G INDICATES NOT LESS THAN
 REQUIRED ON TABLE 602.
  
 2) THE OTHER ISSUE WITH THE EXTERIOR WALLS IT IS NOT
 CLEAR AS TO THE TYPE OF FINISH TO BE APPLIED ON THE
 ADDITION IT APPEARS THE SHEATHING TO BE 5/8" PLYWOOD.
 PLEASE REVIEW SECTION FBC-B 602.3 FOR EXTERIOR WALLS TO
 BE OF NON-COMBUSTIBLE MATERIAL.
  
 3) WHEN PLYWOOD IS TO BE USED AS A EXTERIOR FINISH IT
 MUST MEET THE EXPOSURE DURABILITY CLASSIFICATION.
 2304.6.1 WOOD STRUCTURAL PANEL SHEATHING. WHERE WOOD
 STRUCTURAL PANEL SHEATHING IS USED AS THE EXPOSED
 FINISH ON THE EXTERIOR OF OUTSIDE WALLS, IT SHALL HAVE
 AN EXTERIOR EXPOSURE DURABILITY CLASSIFICATION. WHERE
 WOOD STRUCTURAL PANEL SHEATHING IS USED ON THE EXTERIOR
 OF OUTSIDE WALLS BUT NOT AS THE EXPOSED FINISH, IT
 SHALL BE OF A TYPE MANUFACTURED WITH EXTERIOR GLUE
 (EXPOSURE 1 OR EXTERIOR). WHERE WOOD STRUCTURAL PANEL
 SHEATHING IS USED ELSEWHERE, IT SHALL BE OF A TYPE
 MANUFACTURED WITH INTERMEDIATE OR EXTERIOR GLUE.
  
 4) ADDITIONAL INFORMATION REQUIRED:
 4A) THE PLANS INDICATE THE USE OF A MADE UP STEEL
 COLUMN AND BEAM BUT THE PLANS DO NOT INDICATE THE TYPE
 OF ANCHORS TO BE USED TO ANCHOR THE COLUMN TO THE
 CONCRETE SLAB NOR IS THERE INFORMATION AS TO ANCHORING
 THE BEAM TO THE BUILT UP COLUMN.
  
 4B) PLANS FAIL TO PROVIDE A DETAIL OR SECTION OF THE
 NON-BEARING WALL, AND WALL TO ROOF ASSEMBLY?
  
 4C) PLANS ALSO WILL NEED TO INDICATE IF THERE IS ROOF
 SLOPE TO THE ADDITION?
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 ROOFING ASSEMBLIES.
  
 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) PLEASE REVIEW FBC-B 1503.6 FOR ROOFS WITH NO OVER
 HANG.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  