Plan Review Notes
Plan Review Notes For Permit 10110479
Permit Number 10110479
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-09 11:23:44777 SOUTH FLAGLER DRIVE, SUITE #136 (EAST TOWER)
 PERMIT #10110479
 REVIEW COMMENTS - FIRE
  
 SHEET A1.1
 PROVIDE LIFE SAFETY DATA ENTAILING OCCUPANCY TYPE,
 OCCUPANT LOAD, NUMBER OF EXITS, TRAVEL DISTANCES, DOOR
 HARDWARE ETC.
  
 PROVIDE A FURNITURE LAYOUT.
  
 THE SWING OF RESTROOM DOOR NO.10 OBSTRUCTS MORE THAN 50
 PERCENT OF THE HALLWAY.
  
 SLIDING POCKET DOOR NO. 11 DOES NOT MEET THE EGRESS
 REQUIREMENTS OF CHAPTER 7 OF NFPA 101 - LIFE SAFETY
 CODE.
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION.
  
 PORTABLE FIRE EXTINGUISHERS (2A:10BC) SHALL BE LOCATED
 IN ALONG THE PATH OF EGRESS.
  
  
 SHEET FS0.1
 SPRINKLER DESIGN SHALL CONFORM TO THE 2003 EDITION OF
 NFPA 13 AS IS REFERENCED IN THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION.
  
 PROVIDE WATER SUPPLY DATA (FLOW TEST OR FIRE PUMP TEST
 RESULTS).
  
  
 SHEET FS2.1
 ALL SPRINKLERS INSTALLED ARE REQUIRED TO BE NEW. REUSE
 OF SPRINKLERS IS PROHIBITED. REVISE KEY NOTE NUMBER 1.
  
 PROTECT STORAGE SPACES AS ORDINARY HAZARD. REVISE KEY
 NOTE NUMBER 3 LABELING ALL SPACES AS LIGHT HAZARD.
  
 THIS SPRINKLER SYSTEM IS SUBJECT TO PRESSURES IN EXCESS
 OF 100 PSI. REVISE HANGER LOCATION SCHEDULE AND HANGER
 TYPES TO MEET THE REQUIREMENTS OF NFPA 13 FOR SYSTEM
 PRESSURES GREATER THAN 100 PSI.
  
  
 SHEET E-1
 SHOW THE SCOPE OF THE FIRE ALARM WORK.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR CONTRACTOR'S
 FIRE ALARM SHOP DRAWINGS.
  
  
 SHEET E-2
 PROVIDE ADDITIONAL EXIT SIGNAGE FOR WEST AREA OF OPEN
 OFFICE NO. 106.
  
 THERE DOES NOT APPEAR TO BE EMERGENCY LIGHTING PROVIDED
 FOR CONFERENCE ROOM 102.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730
  