| 2010-12-09 11:23:44 | 777 SOUTH FLAGLER DRIVE, SUITE #136 (EAST TOWER) |
| | PERMIT #10110479 |
| | REVIEW COMMENTS - FIRE |
| | |
| | SHEET A1.1 |
| | PROVIDE LIFE SAFETY DATA ENTAILING OCCUPANCY TYPE, |
| | OCCUPANT LOAD, NUMBER OF EXITS, TRAVEL DISTANCES, DOOR |
| | HARDWARE ETC. |
| | |
| | PROVIDE A FURNITURE LAYOUT. |
| | |
| | THE SWING OF RESTROOM DOOR NO.10 OBSTRUCTS MORE THAN 50 |
| | PERCENT OF THE HALLWAY. |
| | |
| | SLIDING POCKET DOOR NO. 11 DOES NOT MEET THE EGRESS |
| | REQUIREMENTS OF CHAPTER 7 OF NFPA 101 - LIFE SAFETY |
| | CODE. |
| | |
| | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION |
| | CODE 2007 EDITION. |
| | |
| | PORTABLE FIRE EXTINGUISHERS (2A:10BC) SHALL BE LOCATED |
| | IN ALONG THE PATH OF EGRESS. |
| | |
| | |
| | SHEET FS0.1 |
| | SPRINKLER DESIGN SHALL CONFORM TO THE 2003 EDITION OF |
| | NFPA 13 AS IS REFERENCED IN THE FLORIDA FIRE PREVENTION |
| | CODE 2007 EDITION. |
| | |
| | PROVIDE WATER SUPPLY DATA (FLOW TEST OR FIRE PUMP TEST |
| | RESULTS). |
| | |
| | |
| | SHEET FS2.1 |
| | ALL SPRINKLERS INSTALLED ARE REQUIRED TO BE NEW. REUSE |
| | OF SPRINKLERS IS PROHIBITED. REVISE KEY NOTE NUMBER 1. |
| | |
| | PROTECT STORAGE SPACES AS ORDINARY HAZARD. REVISE KEY |
| | NOTE NUMBER 3 LABELING ALL SPACES AS LIGHT HAZARD. |
| | |
| | THIS SPRINKLER SYSTEM IS SUBJECT TO PRESSURES IN EXCESS |
| | OF 100 PSI. REVISE HANGER LOCATION SCHEDULE AND HANGER |
| | TYPES TO MEET THE REQUIREMENTS OF NFPA 13 FOR SYSTEM |
| | PRESSURES GREATER THAN 100 PSI. |
| | |
| | |
| | SHEET E-1 |
| | SHOW THE SCOPE OF THE FIRE ALARM WORK. |
| | |
| | SEPARATE PLANS AND PERMIT REQUIRED FOR CONTRACTOR'S |
| | FIRE ALARM SHOP DRAWINGS. |
| | |
| | |
| | SHEET E-2 |
| | PROVIDE ADDITIONAL EXIT SIGNAGE FOR WEST AREA OF OPEN |
| | OFFICE NO. 106. |
| | |
| | THERE DOES NOT APPEAR TO BE EMERGENCY LIGHTING PROVIDED |
| | FOR CONFERENCE ROOM 102. |
| | |