| Plan Review Notes For Permit 10110476 |
| Permit Number |
10110476 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-20 12:16:30 | RESIDENTIAL (R3) ACCORDION SHUTTERS BUILDING REVIEW | | | CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- AT LEAST ONE MEANS OF ESCAPE FROM THE HOUSE MUST BE | | | PROVIDED WHEN THE ACCORDION SHUTTERS ARE CLOSED. SEC. | | | R310.4 OF 2007 FLORIDA RESIDENTIAL CODE. SPECIFY WHERE | | | IS THE REQUIRED MEANS OF ESCAPE. PARTIAL FLOOR PLAN | | | SUBMITTED SHOWS EGRESS FROM THE BEDROOM. THIS ROOM IS | | | HAVING ACCORDION SHUTTERS ALSO. NEED TO PROVIDE AT | | | LEAST ONE MEANS OF ESCAPE WHEN SHUTTERS ARE UP. | | | | | | 2- A) REVISE ANCHOR SPACING SHOWN ON THE INSTALLATION | | | SCHEDULE WITH THE ANCHOR SPACING SHOWN ON SHUTTERS | | | ANCHOR SCHEDULE ON SHEET 8 OF 16. | | | | | | B) REVISE OPENING SIZE SHOWN ON THE INSTALLATION | | | SCHEDULE WITH THE OPENING SIZE SHOWN ON THE PARTIAL | | | FLOOR PLAN SUBMITTED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|