2011-07-18 15:12:13****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE PLAN PROVIDED SHOWS THE UNIT LOCATED IN ZONE 1
 (FIELD). SEE BELOW DESIGN PRESSURES FROM FIRST
 CORRECTION LIST.
  
 FIELD 49.2PSF
 PERIMETER 82.6PSF
 CORNER 124.3 PSF
  
 2. COMMENT FROM PREVIOUS LIST: ON THE PRODUCT APPROVAL,
 INDICATE WHICH OPTION WILL BE USED ON THIS PROJECT TO
 SHOW COMPLIANCE WITH DESIGN PRESSURE REQUIREMENTS,
 FBC1609. SEE SHEET 2 OF PRODUCT APPROVAL.
  
 2ND REVIEW, RESPONSE IS THAT ALL UNITS ARE STAND DESIGN
 SCHEDULE 1. NOT ALL OF THE OPTIONS COMPLY WITH THE
 REQUIRED DESIGN PRESSURE OF 49.2 PSF. AS REQUESTED,
 PLEASE INDICATE WHICH OPTION IS PROPOSED.
  
  
  