| Plan Review Notes For Permit 10110462 |
| Permit Number |
10110462 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-07-18 15:12:13 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. THE PLAN PROVIDED SHOWS THE UNIT LOCATED IN ZONE 1 | | | (FIELD). SEE BELOW DESIGN PRESSURES FROM FIRST | | | CORRECTION LIST. | | | | | | FIELD 49.2PSF | | | PERIMETER 82.6PSF | | | CORNER 124.3 PSF | | | | | | 2. COMMENT FROM PREVIOUS LIST: ON THE PRODUCT APPROVAL, | | | INDICATE WHICH OPTION WILL BE USED ON THIS PROJECT TO | | | SHOW COMPLIANCE WITH DESIGN PRESSURE REQUIREMENTS, | | | FBC1609. SEE SHEET 2 OF PRODUCT APPROVAL. | | | | | | 2ND REVIEW, RESPONSE IS THAT ALL UNITS ARE STAND DESIGN | | | SCHEDULE 1. NOT ALL OF THE OPTIONS COMPLY WITH THE | | | REQUIRED DESIGN PRESSURE OF 49.2 PSF. AS REQUESTED, | | | PLEASE INDICATE WHICH OPTION IS PROPOSED. | | | | | | | | | |
|