Plan Review Notes
Plan Review Notes For Permit 10110462
Permit Number 10110462
Review Stop B
Sequence Number 1
Notes
Date Text
2010-11-18 12:17:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A PLAN SHOWING PROPOSED LOCATION ON ROOF,
 FBC1609. SHOW DISTANCE FROM ROOF EDGES. THIS IS
 REQUIRED TO DETERMINE ZONE LOCATION AND DESIGN PRESSURE
 REQUIRED WHICH THE ENGINEER HAS SPECIFIED AS:
  
 FIELD 49.2PSF
 PERIMETER 82.6PSF
 CORNER 124.3 PSF
  
 2. ON THE PRODUCT APPROVAL, INDICATE WHICH OPTION WILL
 BE USED ON THIS PROJECT TO SHOW COMPLIANCE WITH DESIGN
 PRESSURE REQUIREMENTS, FBC1609. SEE SHEET 2 OF PRODUCT
 APPROVAL.
  
 3. PLEASE CLARIFY, ARE THE EXISTING UNITS CURRENTLY
 INSTALLED ON THE ROOF? ADDITIONAL ENGINEERING TO VERIFY
 ABILITY OF EXISTING STRUCTURE TO ACCOMODATE THE
 ADDITIONAL LOADS, IF APPLICABLE, MAY BE REQUIRED.
  
  
  