| Plan Review Notes For Permit 10110462 |
| Permit Number |
10110462 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-18 12:17:15 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE A PLAN SHOWING PROPOSED LOCATION ON ROOF, | | | FBC1609. SHOW DISTANCE FROM ROOF EDGES. THIS IS | | | REQUIRED TO DETERMINE ZONE LOCATION AND DESIGN PRESSURE | | | REQUIRED WHICH THE ENGINEER HAS SPECIFIED AS: | | | | | | FIELD 49.2PSF | | | PERIMETER 82.6PSF | | | CORNER 124.3 PSF | | | | | | 2. ON THE PRODUCT APPROVAL, INDICATE WHICH OPTION WILL | | | BE USED ON THIS PROJECT TO SHOW COMPLIANCE WITH DESIGN | | | PRESSURE REQUIREMENTS, FBC1609. SEE SHEET 2 OF PRODUCT | | | APPROVAL. | | | | | | 3. PLEASE CLARIFY, ARE THE EXISTING UNITS CURRENTLY | | | INSTALLED ON THE ROOF? ADDITIONAL ENGINEERING TO VERIFY | | | ABILITY OF EXISTING STRUCTURE TO ACCOMODATE THE | | | ADDITIONAL LOADS, IF APPLICABLE, MAY BE REQUIRED. | | | | | | | | | |
|