| 2010-11-18 15:15:40 | BUILDING PLAN REVIEW | | | PERMIT: 10110453 | | | ADD: 515 N FLAGLER # 701 | | | CONT: FISHER CONTRACTING | | | TEL: (561)691-4716 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | | | | | | | | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) SHEET A-1.0 DOOR SCHEDULE DOOR TYPE (A) PLEASE | | | PROVIDE COMPLIANCE WITH: | | | | | | 2406.3 HAZARDOUS LOCATIONS. THE FOLLOWING SHALL BE | | | CONSIDERED SPECIFIC HAZARDOUS LOCATIONS REQUIRING | | | SAFETY GLAZING MATERIALS: | | | | | | (6). GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL | | | ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF | | | THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER | | | VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND | | | WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS | | | THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE. | | | | | | | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | |
|