Plan Review Notes
Plan Review Notes For Permit 10110445
Permit Number 10110445
Review Stop B
Sequence Number 1
Notes
Date Text
2010-12-21 15:31:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. AAF GUIDE DOES NOT INCLUDE SKYLIGHTS IN THE
 GUIDELINES FOR INSTALLATION. PLEASE ADDRESS.
  
 2. THE SKYLIGHT PRODUCT APPROVAL REQUIRES FASTENING TO
 A ROOF DECK (WITH SHINGLES OR BUR INSTALLED). AN
 ENGINEERING ANALYSIS IS REQUIRED TO DETERMINE DESIGN
 PRESSURE LIMITATIONS FOR THE SKYLIGHT IN THE PROPOSED
 INSTALLATION METHOD. FBC R301, FBC 1609.
  
 3. PROVIDE A DETAIL FOR THE PROPOSED SKYLIGHT
 INSTALLATION (PREPARED BY AN ENGINEER) AS THE PROPOSED
 INSTALLATION IS NOT CONSISTENT WITH THE PRODUCT
 APPROVAL FAC9B72.
  