2010-11-19 07:49:00FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. THE HUB DRAIN FOR THE WATER HEATER PAN DRAIN WILL
 REQUIRE A TRAP PRIMER.
 1002.4 TRAP SEALS. . . WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. A TRAP SEAL PRIMER VALVE SHALL CONFORM TO
 ASSE 1018 OR ASSE 1044.
  
 2. BUSINESS OCCUPANCIES REQUIRE A MINIMUM OF ONE
 DRINKING FOUNTAIN.
 403.1 MINIMUM NUMBER OF FIXTURES. DRINKING FOUNTAINS -
 BUSINESS: 1 PER 100
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR