Plan Review Notes
Plan Review Notes For Permit 10110420
Permit Number 10110420
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2010-12-14 15:18:151920 WEKIVA WAY
 PERMIT #10110420
 REVIEW COMMENTS - FIRE
 APPROVED PROVISO
  
 SECOND FLOOR ACCESS CONTROL:
  
 NO LOCKS (MAG LOCKS, KEYED LOCKS ETC.) PERMITTED ON
 CORRIDOR DOORS #225A OR #247A. EGRESS SHALL BE FREE AT
 ALL TIMES.
  
 SECTION 7.4.1.6 OF THE FLORIDA FIRE PREVENTION CODE
 (NFPA 101 - 2006 EDITION WITH FLORIDA AMENDMENTS)
 REQUIRES ELEVATOR LOBBIES TO HAVE UNRESTRICTED ACCESS
 TO EXTIS. EXIT ACCESS SHALL NOT REQUIRE THE USE OF A
 KEY, TOOL, SPECIAL KNOWLEDGE OR SPECIAL EFFORT.
  
 UNRESTRICTED ACCESS TO TWO EXITS SHALL BE AVAILABLE TO
 ALL OCCUPANTS AT ALL TIMES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved