| 2010-11-19 16:21:12 | 1920 WEKIVA WAY | | | PERMIT #10110420 | | | MASTER #10070788 | | | REVIEW COMMENTS - FIRE | | | | | | NO MANUAL RELEASE BUTTON HAS BEEN PROVIDED INSIDE | | | STORAGE ROOM 121. | | | | | | THE ACCESS CONTROL SYSTEM DEVICES ARE NOT PERMITTED | | | INSIDE THE STAIRS. | | | | | | UPON EXITING THE ELEVATORS ON THE SECOND FLOOR, THE | | | DOORS ARE LOCKED IN THE PATH OF EGRESS TO STAIR 1 AND | | | STAIR 2. THIS IS NOT PERMITTED PER THE REQUIRMENTS OF | | | ACCESS-CONTROLLED EGRESS DOORS. | | | | | | NO MANUAL RELEASE BUTTONS HAVE BEEN PROVIDED ON THE | | | SECOND FLOOR. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 | | | | | | |
|