 REVIEW COMMENTS - FIRE
  
 IN ADDTION TO THE FLORIDA BUILDING CODE, DESIGN SHALL
 CONFORM TO THE REQUIREMENTS OF THE FLORIDA FIRE
 PREVENTION CODE 2007 EDITION.
  
 ALL DEMOLITION WORK TO CONFORM TO THE REQUIREMENTS OF
 NFPA 241.
  
 PROVIDE TACTILE SIGNAGE AT EXITS.
  
 LABEL PERMANENTLY LOCKED DOORS AS "NOT AN EXIT".
  
 PROVIDE SCOPE OF WORK AFFECTING EXISTING FIRE SPRINKLER
 AND/OR FIRE ALARM SYSTEM. PROVIDE NEW/EXISTING DESIGN
 INFORMATION FOR THE FIRE SPRINKLER SYSTEM.
  
 PROVIDE ADDITIONAL INFORMATION FOR THE PADS REFERENCED
 ON SHEET A-1.
  
 COVER SHEET SHOWS AND OCCUPANT LOAD OF 235 PERSONS AND
 19 PERSONS. PLEASE EXPLAIN THE DISCREPANCY.
  
 THE PRINCIPLE EXIT IS DESCRIBED AS HAVING A THUMB TURN
 LOCK. DESCRIBE THE MECHANISM BEING USED TO OPEN THE
 DOOR (NONE, PANIC BAR, LEVER, ETC.)
  
 PROVIDE MAXIMUM STORAGE HEIGHT THAT IS INTENDED FOR
 THIS SPACE.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE ALARM/FIRE
 SPRINKLER SHOP DRAWINGS.
  
  