Text |
| 2010-12-08 13:20:47 | 2505 OKEECHOBEE BOULEVARD, SUITE C | | | PERMIT #10110400 | | | REVIEW COMMENTS - FIRE | | | | | | IN ADDTION TO THE FLORIDA BUILDING CODE, DESIGN SHALL | | | CONFORM TO THE REQUIREMENTS OF THE FLORIDA FIRE | | | PREVENTION CODE 2007 EDITION. | | | | | | ALL DEMOLITION WORK TO CONFORM TO THE REQUIREMENTS OF | | | NFPA 241. | | | | | | PROVIDE TACTILE SIGNAGE AT EXITS. | | | | | | LABEL PERMANENTLY LOCKED DOORS AS "NOT AN EXIT". | | | | | | PROVIDE SCOPE OF WORK AFFECTING EXISTING FIRE SPRINKLER | | | AND/OR FIRE ALARM SYSTEM. PROVIDE NEW/EXISTING DESIGN | | | INFORMATION FOR THE FIRE SPRINKLER SYSTEM. | | | | | | PROVIDE ADDITIONAL INFORMATION FOR THE PADS REFERENCED | | | ON SHEET A-1. | | | | | | COVER SHEET SHOWS AND OCCUPANT LOAD OF 235 PERSONS AND | | | 19 PERSONS. PLEASE EXPLAIN THE DISCREPANCY. | | | | | | THE PRINCIPLE EXIT IS DESCRIBED AS HAVING A THUMB TURN | | | LOCK. DESCRIBE THE MECHANISM BEING USED TO OPEN THE | | | DOOR (NONE, PANIC BAR, LEVER, ETC.) | | | | | | PROVIDE MAXIMUM STORAGE HEIGHT THAT IS INTENDED FOR | | | THIS SPACE. | | | | | | SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE ALARM/FIRE | | | SPRINKLER SHOP DRAWINGS. | | | | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|