Plan Review Notes
Plan Review Notes For Permit 10110391
Permit Number 10110391
Review Stop B
Sequence Number 1
Notes
Date Text
2010-11-19 13:44:39****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A PLAN WHICH SHOWS EXISTING CONDITIONS. IT
 IS NOT CLEAR WHETHER THE DOOR WITH SIDELITE IS
 REPLACING A DOUBLE DOOR OR SINGLE DOOR WITH SIDELIGHT.
 IT IS NOT CLEAR HOW THIS AFFECTS EXITING CAPACITY.
  
 2. THE PROPERTY ADDRESS HAS EXPIRED PERMITS, PLEASE
 ADDRESS.
  
 3. IMPACT PROTECTION REQUIRED, FBC1609.1.4. EITHER
 PROVIDE PRODUCT APPROVALS FOR IMPACT RESISTANT FIXED
 GLASS OR SHUTTERS ARE REQUIRED.
  
 4. IF SHUTTERS ARE PROPOSED, PROVIDE PRODUCT APPROVALS
 AND, IF SHUTTERS ARE USED, COMPLETE THE SAMPLE
 INSTALLATION SCHEDULE (AVAILABLE IN THE LOBBY AND AT HT
 TP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_IN
 STALLATION.PDF). A LIFE SAFETY PLAN WILL BE REQUIRED TO
 SHOW HOW EXITING IS AFFECTED. PLEASE NOTE THAT THERE IS
 NO PROVISION FOR SHUTTERS BLOCKING REQUIRED EXITS IN
 THE BUILDING CODE. SEE FBC1003.6, MEANS OF EGRESS
 CONTINUITY.
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved