Plan Review Notes
Plan Review Notes For Permit 10110375
Permit Number 10110375
Review Stop P
Sequence Number 1
Notes
Date Text
2010-12-03 08:28:25DENIED BY PLUMBING
  
 1) THE PLANS SPECIFY A 2 HP INTELLIFLO VARIABLE SPEED
 PUMP WHICH REQUIRES THE MAXIMUM FLOW RATE OF THE PUMP
 TO BE USED IN CALCULATIONS. THE PIPING SCHEMATIC SHOWS
 3" PIPE ON THE SPA SUCTION LINES AND THE MAIN DRAIN
 DETAIL SPECIFIES 2" BRANCH PIPING BETWEEN THE TWO MAIN
 DRAINS. PLEASE CLARIFY. THE SPA MAIN DRAIN BRANCH
 PIPING BETWEEN THE TWO MAIN DRAINS IS LIMITED TO A
 MAXIMUM OF 6 FEET PER SECOND WHEN ONE OF THE PAIR IS
 BLOCKED PER ANSI/APSP-7. MAXIMUM OUTLET SIZE ON THE
 MANUFACTURED MAIN DRAIN SUMPS IS TYPICALLY 2-1/2" AND
 IS CONSIDERED PART OF THE MAIN DRAIN BRANCH PIPING PER
 DEFINITION 3.5 OF ANSI/APSP-7 2006. THEREFORE, THE
 MAXIMUM BRANCH PIPING SIZE IS 2-1/2". UNLESS TDH
 CALCULATIONS ARE SUBMITTED THE MAXIMUM FLOW RATE OF THE
 PUMP WILL BE USED TO DETERMINE THE WATER VELOCITY.
 PLEASE SHOW HOW THE POOL PIPING WILL COMPLY WITH
 ANSI/APSP-7 SECTION 4.4 AND FBC R4101.6.3.
  
 2) SUBMIT 2 COPIES OF THE SPECIFICATIONS FOR THE POOL
 PUMP INCLUDING THE PUMP CURVE.
  
 3) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FOR THE SYSTEM OR DESIGN THE SYSTEM FOR
 THE MAXIMUM FLOW RATE OF THE PUMP.
  