| Plan Review Notes For Permit 10110345 |
| Permit Number |
10110345 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-19 13:26:39 | BUILDING PROVISO: | | | | | | 1) 2007 FBC-BUILDING 712.4.1 HORIZONTAL (FLOOR) | | | ASSEMBLIES. PENETRATIONS OF A FLOOR, FLOOR/CEILING | | | ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING | | | ASSEMBLY SHALL BE PROTECTED IN ACCORDANCE WITH SECTION | | | 707. | | | | | | 712.4.1.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. | | | THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED | | | THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND | | | TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A | | | MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF | | | WATER (2.49 PA). THE SYSTEM SHALL HAVE AN F-RATING AND | | | A T-RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN | | | THE REQUIRED RATING OF THE FLOOR PENETRATED. PLEASE | | | PROVIDE TO INSPECTOR CUT SHEETS FOR PRODUCTS INSTALLED | | | TO MAINTAIN THE RATING OF THE FLOOR SYSTEM. |
|