Plan Review Notes
Plan Review Notes For Permit 10110345
Permit Number 10110345
Review Stop B
Sequence Number 1
Notes
Date Text
2010-11-19 13:26:39BUILDING PROVISO:
  
 1) 2007 FBC-BUILDING 712.4.1 HORIZONTAL (FLOOR)
 ASSEMBLIES. PENETRATIONS OF A FLOOR, FLOOR/CEILING
 ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING
 ASSEMBLY SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
 707.
  
 712.4.1.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER (2.49 PA). THE SYSTEM SHALL HAVE AN F-RATING AND
 A T-RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN
 THE REQUIRED RATING OF THE FLOOR PENETRATED. PLEASE
 PROVIDE TO INSPECTOR CUT SHEETS FOR PRODUCTS INSTALLED
 TO MAINTAIN THE RATING OF THE FLOOR SYSTEM.