| Plan Review Notes For Permit 10110305 |
| Permit Number |
10110305 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-13 09:21:54 | 1009 BANYAN BOULEVARD | | | PERMIT NUMBER 10110305 | | | AQUA AMMONIA CHEMICAL FEED AND STORAGE SYSTEM | | | | | | | | | 1. PLEASE PROVIDE MATERIAL SAFETY DATA SHEETS (MSDS) | | | FOR THE TEMPORARY AND PERMANENT AQUA AMMONIA PRODUCT. | | | | | | 2. PLEASE SUBMIT A HAZARDOUS MATERIALS MANAGEMENT PLAN | | | (HMMP) TO THIS OFFICE FOR REVIEW. | | | | | | 3. ALL DEMOLITION, RENOVATION, AND CONSTRUCTION SHALL | | | COMPLY WITH NFPA 241. | | | | | | 4. CARE IS TO BE TAKEN WHEN REMOVING THE AMMONIA TANKS | | | AND ALL APPURTENANT EQUIPMENT AND ELECTRICAL SYSTEMS | | | AND DEVICES DESCRIBED ON SHEET M-1. | | | | | | 5. THE AQUA AMMONIA BULK AND DAY TANKS ARE TO BE | | | PROPERLY LABELED WITH TANK CONTENTS AND QUANTITIES. | | | | | | 6. IT WAS NOTED THAT CONTAINMENT CURBS ARE LOCATED | | | DIRECTLY IN-FRONT OF DOORS USED FOR EXISTING. | | | | | | 7. PLEASE INCLUDE "NO SMOKING SIGNS" FOR BUILDING. | | | | | | 8. ALL AMMONIA IS TO BE STORED, HANDLED, AND USED IN | | | ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL | | | GUIDELINES. | | | | | | 9. PLEASE INDICATE ALL SAFETY EQUIPMENT CONTAINED ON | | | THE INSIDE AND OUTSIDE OF THE BUILDING. | | | | | | 10. PLEASE INDICATE OCCUPANT LOADS FOR THE BUILDING. | | | | | | 11. MORE DETAILS REQUIRED ON THE STORAGE VESSELS | | | PLANNED FOR USE. | | | | | | 12. PLEASE DESCRIBE EMERGENCY PROCEDURES. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | | | | |
|