2010-12-13 09:21:541009 BANYAN BOULEVARD
 PERMIT NUMBER 10110305
 AQUA AMMONIA CHEMICAL FEED AND STORAGE SYSTEM
  
  
 1. PLEASE PROVIDE MATERIAL SAFETY DATA SHEETS (MSDS)
 FOR THE TEMPORARY AND PERMANENT AQUA AMMONIA PRODUCT.
  
 2. PLEASE SUBMIT A HAZARDOUS MATERIALS MANAGEMENT PLAN
 (HMMP) TO THIS OFFICE FOR REVIEW.
  
 3. ALL DEMOLITION, RENOVATION, AND CONSTRUCTION SHALL
 COMPLY WITH NFPA 241.
  
 4. CARE IS TO BE TAKEN WHEN REMOVING THE AMMONIA TANKS
 AND ALL APPURTENANT EQUIPMENT AND ELECTRICAL SYSTEMS
 AND DEVICES DESCRIBED ON SHEET M-1.
  
 5. THE AQUA AMMONIA BULK AND DAY TANKS ARE TO BE
 PROPERLY LABELED WITH TANK CONTENTS AND QUANTITIES.
  
 6. IT WAS NOTED THAT CONTAINMENT CURBS ARE LOCATED
 DIRECTLY IN-FRONT OF DOORS USED FOR EXISTING.
  
 7. PLEASE INCLUDE "NO SMOKING SIGNS" FOR BUILDING.
  
 8. ALL AMMONIA IS TO BE STORED, HANDLED, AND USED IN
 ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL
 GUIDELINES.
  
 9. PLEASE INDICATE ALL SAFETY EQUIPMENT CONTAINED ON
 THE INSIDE AND OUTSIDE OF THE BUILDING.
  
 10. PLEASE INDICATE OCCUPANT LOADS FOR THE BUILDING.
  
 11. MORE DETAILS REQUIRED ON THE STORAGE VESSELS
 PLANNED FOR USE.
  
 12. PLEASE DESCRIBE EMERGENCY PROCEDURES.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  