| Plan Review Notes For Permit 10110291 |
| Permit Number |
10110291 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-03 14:09:08 | 1. LOCATE ELECTRICAL PANEL ON PLANS. ACCESS TO THE | | | ELECTRICAL PANEL SHALL PROVIDE SAFE WORKING CLEARANCE | | | PER NEC, 110-26. | | | 2. PROVIDE DETAILS REGARDING THE SIZE OF THE EXISTING | | | ELECTRICAL SERVICE INCLUDING FEEDERS. NEC, ARTICLE 220 | | | 3. PROVIDE AN ELECTRICAL PANEL SCHEDULE SHOWING THE | | | SIZE OF WIRING AND OVER CURRENT PROTECTION FOR ALL | | | BRANCH CIRCUITS. NEC, 210-7(C) | | | R. LECKY, ELECTRICAL PLANS EXAMINER, WPB CONSTRUCTION | | | SERVICES . PHONE 561-805-6718 |
|