Plan Review Notes
Plan Review Notes For Permit 10110291
Permit Number 10110291
Review Stop B
Sequence Number 1
Notes
Date Text
2010-11-19 10:58:46BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 PLANS DO NOT INDICATE ANY INFORMATION ON THE NEW FRAMED
 METAL STUD WALL. PLEASE PROVIDE THE SIZE (WIDTH) OF
 STEEL STUD, GUAGE OF STUD, AND SPACING OF STEEL STUDS
 AND THE DESIGN CRITERIA, MINIMUM DESIGN LOAD, AND
 MAXIMUM ALLOWABLE DEFECTION.
 2007 FBC- BUILDING/ 2009 REVISIONS SECTION 2508.1,
 TABLE 2508.1 & ASME C754-04 STEEL FRAMING FOR STEEL
 STUDS.
  
 JIM WITMER C. B. O.