| 2011-01-12 13:05:28 | 525 OKEECHOBEE BOULEVARD, SUITE #750 |
| | PERMIT #10110288 |
| | REVIEW COMMENTS - FIRE |
| | |
| | *****APPROVED WITH PROVISIOINS***** |
| | |
| | PROVIDE 90-MINUTE FIRE-RATED DOORS FOR OPENING |
| | PROTECTION IN NEW 2-HOUR FIRE-RATED WALL ASSEMBLY. THE |
| | DOORS AFFECTED ARE 701 AND 714. THE PROPOSED SPRINKLER |
| | WATER CURTAIN AT THE MAIN ENTRY PROVIDES ONLY A 1-HOUR |
| | SEPARATION EQUIVALENT AND IS ONLY APPLICABLE TO ATRIUM |
| | GLAZING CURTAIN WALLS. TYCO MODEL WS WINDOW SPRINKLERS |
| | ARE THE ONLY UL-LISTED SPRINKLERS THAT CAN PROVIDE AN |
| | EQUIVALENT TWO-HOUR FIRE SEPARATION; HOWEVER,THESE |
| | SPRINKLERS ARE ONLY LISTED TO PROTECT WINDOWS, NOT |
| | DOORS. |
| | |
| | THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE |
| | USES THE 2006 EDITION OF THE LIFE SAFETY CODE - NFPA |
| | 101 WITH FLORIDA AMENDMENTS. THE COVER SHEET REFERENCES |
| | THE 2003 EDITION OF NFPA 101. |
| | |
| | CONSTRUCTION DOCUMENTS ARE NEEDED FOR THE MODIFICATION |
| | OF THE FIRE ALARM AND AUTOMATIC SPRINKLER SYSTEMS. |
| | ADDITIONALLY, SEPARATE PLANS AND PERMITS WILL BE NEEDED |
| | FOR THE FIRE ALARM AND SPRINKLER SYSTEM SHOP DRAWINGS. |
| | |
| | THE ACCESS-CONTROLLED EGRESS SYSTEM SHALL BE INTEGRATED |
| | WITH THE BUILDING FIRE ALARM SYSTEM AND FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT EXIT DOORS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | (561) 805-6730 |