| 2011-01-06 10:33:36 | 525 OKEECHOBEE BOULEVARD, SUITE #750 |
| | PERMIT #10110288 |
| | REVIEW COMMENTS - FIRE |
| | |
| | REPEAT COMMENT: THE 2007 EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE USES THE 2006 EDITION OF THE LIFE |
| | SAFETY CODE - NFPA 101 WITH FLORIDA AMENDMENTS. THE |
| | COVER SHEET REFERENCES THE 2003 EDITION OF NFPA 101. |
| | |
| | REPEAT COMMENT: TO OBTAIN A BUILDING PERMIT, |
| | CONSTRUCTION DOCUMENTS ARE NEEDED FOR THE MODIFICATION |
| | OF THE FIRE ALARM AND AUTOMATIC SPRINKLER SYSTEMS. |
| | ADDITIONALLY, SEPARATE PLANS AND PERMITS WILL BE NEEDED |
| | FOR THE FIRE ALARM AND SPRINKLER SYSTEM SHOP DRAWINGS. |
| | |
| | REPEAT COMMENT: THE ACCESS-CONTROLLED EGRESS SYSTEM |
| | SHALL BE INTEGRATED WITH THE BUILDING FIRE ALARM SYSTEM |
| | AND FIRE SPRINKLER SYSTEM. |
| | |
| | NEW COMMENT: PROVIDE TACTILE SIGNAGE AT EXIT DOORS. |
| | |
| | NOTE: THE CURRENT EXIT ACCESS CONFIGURATION CREATES A |
| | COMMON PATH OF TRAVEL GREATER THAN 100 FEET. THE TWO |
| | DOORS (701 & 714) FROM THE TENANT SUITE ARE STILL |
| | CONSIDERED EXIT ACCESS AND NOT EXIT. |
| | |
| | THE DESIGN TEAM HAS PROPOSED THE INSTALLATION OF A |
| | TWO-HOUR FIRE-RATED WALL SEPARATION BETWEEN TENANT |
| | SUITE #750 AND THE EXIT ACCESS CORRIDOR. THIS |
| | ALTERNATIVE METHOD IS SUBMITTED AS A REQUEST FOR |
| | EQUIVALENCY. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | (561) 805-6730 |